155 lines
3.6 KiB
C
155 lines
3.6 KiB
C
/************************
|
|
*
|
|
* This file contains the settings for the ethernet module, GPIO pins for the LCD screen, the states, the data structure, the normal
|
|
* conditions for the inputs, the alarm priority they are associated with, the MODBUS modules, and the text strings used for the LCD display
|
|
*
|
|
*************************/
|
|
|
|
|
|
/******
|
|
* MAC address for the ethernet module
|
|
*
|
|
******/
|
|
byte mac[] = {0x60, 0x52, 0xD0, 0x07, 0x17, 0x14};
|
|
|
|
|
|
/******
|
|
* GPIO pins for the LCD screen
|
|
*
|
|
******/
|
|
const int rs = 0, en = 1, d4 = 11, d5 = 12, d6 = 13, d7 = 14;
|
|
|
|
|
|
/******
|
|
*
|
|
* Number of states
|
|
* (CAUTION CHANGING THIS!!!)
|
|
*
|
|
******/
|
|
enum STATES{
|
|
startup,
|
|
normal,
|
|
trouble1,
|
|
trouble2,
|
|
trouble3
|
|
};
|
|
|
|
|
|
/******
|
|
*
|
|
* Input buffer and values
|
|
*
|
|
******/
|
|
char buf[2];
|
|
uint16_t read;
|
|
int input[16];
|
|
float analog1;
|
|
float analog2;
|
|
float analog3;
|
|
float tSniffer;
|
|
float vacuum;
|
|
float subPump;
|
|
|
|
|
|
/******
|
|
* Initial state of the interlock
|
|
*
|
|
******/
|
|
STATES newState = normal;
|
|
STATES currentState = startup;
|
|
|
|
|
|
/******
|
|
* Specify the trouble condition each input would trigger
|
|
*
|
|
******/
|
|
const STATES alarm[16] = {
|
|
normal, // Reset switch
|
|
trouble3, // Emergency source trip switch
|
|
trouble1, // Cage door contact
|
|
trouble3, // Fume hood flow switch
|
|
trouble2, // Vacuum condition - gnd
|
|
trouble3, // Tritium monitor
|
|
trouble3, // Control Room Emergency Switch
|
|
trouble3, // Power failure
|
|
trouble3, // Coolant flow - gnd
|
|
trouble2, // Vacuum condition - mid
|
|
normal, // UNUSED
|
|
trouble3, // Coolant flow - high
|
|
trouble3, // Smoke detector - high
|
|
normal, // UNUSED
|
|
normal, // UNUSED
|
|
normal // UNUSED
|
|
|
|
};
|
|
|
|
|
|
/******
|
|
* Specify the normal condition for each input
|
|
*
|
|
*****/
|
|
bool input_normal[16] = {
|
|
|
|
OPEN, // 0 , lvl= 0, Reset switch
|
|
CLOSED, // 1 , lvl= 3, Emergency source trip switch
|
|
CLOSED, // 2 , lvl= 1, Cage door contact, level-1
|
|
OPEN, // 3 , lvl= 3, Fume hood flow switch, level-3
|
|
OPEN, // 4 , lvl= 2, Vacuum condition - gnd, level-2
|
|
CLOSED, // 5 , lvl= 3, Tritium monitor
|
|
CLOSED, // 6 , lvl= 3, Control Room Emergency Switch
|
|
CLOSED, // 7 , lvl= 3, Power failure
|
|
CLOSED, // 8 , lvl= 2, Coolant flow - gnd
|
|
OPEN, // 9 , lvl= 2, Vacuum condition - mid
|
|
OPEN, // 10 , lvl= 0, UNUSED
|
|
CLOSED, // 11 , lvl= 2, Coolant flow - high
|
|
OPEN, // 12 , lvl= 3, Smoke detector - high
|
|
OPEN, // 13 , lvl= 0, UNUSED
|
|
OPEN, // 14 , lvl= 0, UNUSED
|
|
OPEN // 15 , lvl= 0, UNUSED
|
|
|
|
};
|
|
|
|
/******
|
|
* Array to track the output status for updating interfaces
|
|
*
|
|
******/
|
|
bool output[16] = {0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0};
|
|
|
|
|
|
/******
|
|
* Specify which modules are on the MODBUS
|
|
*
|
|
******/
|
|
const char* RollCall[] = {
|
|
"P1-16ND3", "P1-08TRS", "P1-08TRS", "P1-04ADL-2"
|
|
};
|
|
|
|
|
|
/******
|
|
* Text strings for the LCD Display
|
|
*
|
|
******/
|
|
String state_txt[] = {"Rebooting...",
|
|
"Source Normal",
|
|
"Cage Door Trip!",
|
|
"Vacuum Trip!",
|
|
"Source Trip!"};
|
|
|
|
String in_txt[] = { "Reset Button",
|
|
"Emergency Switch",
|
|
"Cage Door Open",
|
|
"Fume Hood Flow",
|
|
"Vacuum Gauge 2",
|
|
"Tritium Monitor",
|
|
"Control Room Emergency Switch",
|
|
"Bldg Power Fail",
|
|
"Coolant Flow 2",
|
|
"Vacuum Gauge 1",
|
|
"error: port map",
|
|
"Coolant Flow 1",
|
|
"Smoke at Source",
|
|
"error: port map",
|
|
"error: port map",
|
|
"error: port map",
|
|
""};
|