Multi-SNICS_Interlock/interlock/config.h

155 lines
3.6 KiB
C

/************************
*
* This file contains the settings for the ethernet module, GPIO pins for the LCD screen, the states, the data structure, the normal
* conditions for the inputs, the alarm priority they are associated with, the MODBUS modules, and the text strings used for the LCD display
*
*************************/
/******
* MAC address for the ethernet module
*
******/
byte mac[] = {0x60, 0x52, 0xD0, 0x07, 0x17, 0x14};
/******
* GPIO pins for the LCD screen
*
******/
const int rs = 0, en = 1, d4 = 11, d5 = 12, d6 = 13, d7 = 14;
/******
*
* Number of states
* (CAUTION CHANGING THIS!!!)
*
******/
enum STATES{
startup,
normal,
trouble1,
trouble2,
trouble3
};
/******
*
* Input buffer and values
*
******/
char buf[2];
uint16_t read;
int input[16];
float analog1;
float analog2;
float analog3;
float tSniffer;
float vacuum;
float subPump;
/******
* Initial state of the interlock
*
******/
STATES newState = normal;
STATES currentState = startup;
/******
* Specify the trouble condition each input would trigger
*
******/
const STATES alarm[16] = {
normal, // Reset switch
trouble3, // Emergency source trip switch
trouble1, // Cage door contact
trouble3, // Fume hood flow switch
trouble2, // Vacuum condition - gnd
trouble3, // Tritium monitor
normal, // UNUSED
trouble3, // Power failure
trouble3, // Coolant flow - gnd
trouble2, // Vacuum condition - mid
normal, // UNUSED
trouble3, // Coolant flow - high
trouble3, // Smoke detector - high
normal, // UNUSED
normal, // UNUSED
normal // UNUSED
};
/******
* Specify the normal condition for each input
*
*****/
bool input_normal[16] = {
OPEN, // 0 , lvl= 0, Reset switch
CLOSED, // 1 , lvl= 3, Emergency source trip switch
CLOSED, // 2 , lvl= 1, Cage door contact, level-1
CLOSED, // 3 , lvl= 3, Fume hood flow switch, level-3
OPEN, // 4 , lvl= 2, Vacuum condition - gnd, level-2
CLOSED, // 5 , lvl= 3, Tritium monitor
OPEN, // 6 , lvl= 0, UNUSED
CLOSED, // 7 , lvl= 3, Power failure
CLOSED, // 8 , lvl= 2, Coolant flow - gnd
OPEN, // 9 , lvl= 2, Vacuum condition - mid
OPEN, // 10 , lvl= 0, UNUSED
CLOSED, // 11 , lvl= 2, Coolant flow - high
OPEN, // 12 , lvl= 3, Smoke detector - high
OPEN, // 13 , lvl= 0, UNUSED
OPEN, // 14 , lvl= 0, UNUSED
OPEN // 15 , lvl= 0, UNUSED
};
/******
* Array to track the output status for updating interfaces
*
******/
bool output[16] = {0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0};
/******
* Specify which modules are on the MODBUS
*
******/
const char* RollCall[] = {
"P1-16ND3", "P1-08TRS", "P1-08TRS", "P1-04ADL-2"
};
/******
* Text strings for the LCD Display
*
******/
String state_txt[] = {"Rebooting...",
"Source Normal",
"Cage Door Trip!",
"Vacuum Trip!",
"Source Trip!"};
String in_txt[] = { "Reset Button",
"Emergency Switch",
"Cage Door Open",
"Fume Hood Flow",
"Vacuum Gauge 2",
"Tritium Monitor",
"error: port map",
"Bldg Power Fail",
"Coolant Flow 2",
"Vacuum Gauge 1",
"error: port map",
"Coolant Flow 1",
"Smoke at Source",
"error: port map",
"error: port map",
"error: port map",
""};