ANASEN

From FSU Fox's Lab Wiki
Revision as of 17:49, 11 July 2022 by Rtang (talk | contribs)
Jump to navigation Jump to search

HV supply

IP

128.186.111.101

Iseg HV with Wiener Mpod

The Iseg HV modules are using Mpod crate. A Mpod-C (controller) is used to control the HV module.

The Mpod-C can be controlled via ethernet, USB, or CAN. For the ethernet, it requires an IP.

to control the Mpod-C via USB (say, setting up the IP), in Windows, install the MUSEController.

SNMP

in linux, install snmp

sudo apt install snmp

copy the WIENER-CRATE-MIB.txt into /usr/share/snmp/mibs/

example syntax
~>snmpget -v 2c -m +WIENER-CRATE-MIB -c guru 128.186.111.101 outputMeasurementSenseVoltage.u1
WIENER-CRATE-MIB::outputMeasurementSenseVoltage.u1 = Opaque: Float: 0.000000 V
~>snmpset -v 2c -m +WIENER-CRATE-MIB -c guru 128.186.111.101 outputVoltage.u0 F 0.0
WIENER-CRATE-MIB::outputVoltage.u0 = Opaque: Float: 0.000000 V