Contents
1 Help Call List for Evenings/Weekends/Holidays
2 WATER COOLING SYSTEM
3 TANDEM/SNICS POWER FAILURE PROCEDURES
4 Cryopump Regeneration Procedure
5 Cable Changes for Switching Ion Source
6 Tuning Beam out of the SNICS Source
7 Typical Cathode Behavior
8 SNICS Temporary Turn Down
9 SNICS Turn Down to Idle Mode
10 SNICS Cathode Change Instructions
11 Outgassing a New Ionizer
12 Ion Source Shutdown and Disassembly
13 RF Source Operation
13.1 Operating principle
13.2 RF Discharge Contaminants
13.3 Summary of operation
14 RF Source Tuning Instructions with the PC
14.1 Focusing and Steering Control
14.2 Optimizing on Source Cup-2
15 This page for Polarized Lithium Stuff
16 Hardware/Cable Changes for Switching Target Rooms
16.1 From the Tandem Target Room to the LINAC Target Room
16.2 From LINAC Target Room to Tandem Target Room
17 Hardware/Cable Changes for Choosing a BeamLine out of the Switching Magnets
17.1 LINAC Target Room Switching Magnet
17.2 Tandem Target Room Switching Magnet
18 Tandem Beamline SF6 Gas Security Ball Valves
19 Tandem Beamline Vacuum Protection System
20 Tandem Pelletron Interlock Panel
21 Terminal Potential Stabilizer
22 Operating Instructions for the Tandem Pelletron
22.1 To Turn the Tandem Pelletron On
22.2 TO TURN OFF THE Tandem PELLETRON
22.3 TO CHANGE THE TERMINAL POTENTIAL
23 Extended Tandem Pelletron Shutdown
24 Terminal Stripper Foil Changer
25 Terminal Foil Band Changer
26 LETTING ACCELERATOR TUBES UP TO DRY NITROGEN
27 Pumping down the Accelerator Tubes
28 Tandem Pressure Vessel Sulfur Hex Alarm Circuit Description
29 Voltage Conditioning the Tandem
30 Worthington Compressor
31 EMERGENCY VALVE CLOSURES
32 Equalizing the SF6 gas to the outside Storage Vessel
33 Compressing the SF6 to the Storage Vessel
34 Vacuum Pump boosting for the Compressor
35 Shutoff Procedure
36 Venting the Tandem to Air
37 Removing Air from the Tandem
38 Equalizing SF6 into the Tandem
39 Compressing SF6 into the Tandem
40 Adding SF6 to the Inventory from Cylinders
40.1 Adding SF6 directly to the Tandem From Cylinders
40.2 Removing the SF6 remaining in the cylinders at Tandem pressure
41 SF6 Gas Drying
42 SF6 Leak Checking Gun
1 Help Call List for Evenings/Weekends/Holidays
Situations arise out of normal staff working hours that require attention
by staff personnel. Due to the limited time available to visiting outside
user groups and their unfamiliarity with the laboratory equipment the staff
is more willing to concede their personal time to ensure the acquisition
of data by these groups. Out of consideration to staff members and their
families it is necessary to assess the situation and determine whether
or not a call to a staff member's home is warranted. In house users should
not expect the staff to come into the lab outside of normal hours unless
extenuating circumstances are deemed acceptable by more than the currently
stalled experimental group. Please use the following as a guide when considering
calling the staff at home.
O.K. to Call
Failure of equipment that could create a
potentially dangerous situation to lab personnel and
experimenters or that may result in extended down time
for the accelerators. Examples of these types of
failures might concern compressed air service, SF6
leaks, cryostat vacuum integrity, cryogenic fluid
spills/leaks, Helium liquefier failures, cooling water
interruptions, power outage, electrical failures,
mechanical or structural failures. Abnormal behavior
by equipment that suggest failure is imminent unless
someone intervenes should also be considered -
especially potentially expensive failures that can be
avoided if they are quickly rectified.
Not O.K. to Call
These problems are typically due to an inability to
take data. Data acquisition problems may be due to
Ion Sources, Tandem, Linac or computers. In house
users are expected to familiarize themselves with the
equipment so that they can diagnose and rectify the
more common problems such as resonators out of lock,
cryopump regeneration, Ion source adjustment, stripper
foil fatigue, etc. The staff is dedicated to ensuring
the facilities ability to produce data for the
experimental groups and often a quick phone call can
enable the experiment to resume, however, consider the
time of day and the complexity of the fault before
picking up the phone.
2 WATER COOLING SYSTEM
The recirculating cooling water in the lab employs a heat exchanger,
temperature controlled valve, filter and pump to provide cold water service
to equipment. Bending magnets, PIN Diode Pulsars, Sputter Source (SNICS),
Tandem are some of the equipment that require cooling to remain in operation.
The recirculating loop is automatically topped off by city or chilled water
depending on availability. Should there be an interruption of water service
to the building the following instructions apply. The valves are located
in the Southeast corner of the Tandem Vault
When Chilled Water Service is Interrupted:
Open the two valves labeled ``city water" and close the two valves
labeled ``chilled water". This changes the heat exchanger over to city
water in for cooling the recirculating loop and then out to a drain. Change
the recirculating water top off valve to the position labeled ``city".
When Chilled Water Service Returns:
Open the two valves labeled ``chilled water" and close the two valves
labeled ``city water". This changes the heat exchanger back to chilled
water for cooling the recirculating loop.
Recirculator Pump Goes Off and Will Not Restart:
The recirculating loop can be fed directly by city water in an emergency
situation. The valves C1 and D1 are located in the Southeast corner of
the Tandem Vault. The valves C2, D2 and D3 are located in the Gas Handling
Room. C2 and D3 are located by the L.E. vault entrance and D2 is located
ear the floor at the middle of the East wall.
To bypass the recirculating loops water pump first ensure its power
switch, positioned on the wall over the pump, is turned off. Close the
valves C1 and C2. Open valve D1 and D2 first and then open D3.
When the recirculator pump is operational again it should be placed
back into service. Close valve D3 first and the close D1 and D2. Open
valves C1 and C2. Now turn the recirculating pump back on. The system
should now be providing cool water via the heat exchanger.
3 TANDEM/SNICS POWER FAILURE PROCEDURES
When the mains fail the emergency generator should start automatically.
If the emergency lights come on, the generator is running correctly. The
changeover breaker should switch automatically and restore power to all
pump circuits. If this does not occur, the change over breaker, located
on the West wall of the accelerator vault between the L.E. door and the
sink, should be assisted with a 2 by 4. Note: In the emergency power
position the central arm should be down.
When emergency power is available at the pumping stations a number of
things should be checked:
- Check that the recirculating pump, located just to
the South of the L.E. door in the accelerator vault,
is running. Restart if necessary. See water cooling
system.
- Check that source pumping stations are operating
normally. Restart pumps and reopen valves as
necessary.
- Check the turbo pump at the H.E. end, it may have
tripped and be coasting down. It should be restarted.
- Check cryopumps. If the supply was only interrupted
for a few seconds the compressors will restart
automatically but the input and output pressures will
remain the same for approximately one minute then the
unit will switch and normal pressures will be
reestablished. When this occurs the coldhead will
restart and the vibration of this motion will be felt
at the cold head. If the power is off long enough for
the pump to start to warm and outgas, it will have to
be started again. See the section on cryopump head
regeneration.
- The pumps in the target room should be checked to
ensure that they are running normally. Restart or
close off as necessary.
When mains voltage is restored the changeover breaker will wait a short
time, to ensure that the supply will probably remain on, and then will
automatically change over and the emergency generator will shutdown. If
the breaker hangs up it can be assisted up with the 4 by 2. When the mains
supply has been restored to the pumping stations the
previous checks should be repeated. When all vacuums are normal the beamline
valves should be checked and reopened as necessary. Make sure that the
vacuum is good on both sides before opening any valve.
4 Cryopump Regeneration Procedure
A cryopump is a capture pump and requires regeneration when capacity
is reached. Indications of the pump having reached capacity include a
loss of pumping speed and a warming of the 22 Kelvin cryopanel. To regenerate
the cold head:
- Isolate the pump from the vacuum chamber; usually, a
gate valve is used. Ensure that the valve control is
in protected mode if there is an interlock system in
use.
- Turn off cold head power. If a portable compressor is
used, this should be turned off as well. CTI systems
have separate switches for the compressor and cold
head, while APD has only a single switch. In the new
target room, the coldheads are powered with a homemade
box.
- Obtain a source of dry Nitrogen. For example, at the
low energy end of the Tandem, there is a 1/4" nylon
tube with a rubber stopper available. Nitrogen for
the 90° magnet and switching magnet cryopumps can be
obtained from a similar tube located directly between
the quadrupoles at the high energy end of the Tandem.
In the new target room, you are on your own, however,
bottled nitrogen is available.
- Purge the pump with nitrogen by inserting the stopper
into the roughing port and opening the roughing valve.
Allow the nitrogen to flow through the pump and out
the relief valve. Allow the pump to purge for about
30 minutes.
- Obtain and install a heat tape around the pump. Start
the heat tape when the purge is started.
- Allow the pump's internal cryopanel to reach ambient
temperature. This should take at least 2 hours. If
time is not critical, allow 4 to 6 hours for warm up.
- After warm up is complete, purge the pump with
nitrogen for a few minutes to remove any evolved gases
that may still be in the pump.
- Using an oil free roughing system, rough out the
cryopump. Best performance is observed when a good
rough vacuum is obtained. Pumping should continue for
at least 20 minutes and until the following criteria
are met:
- The cryopump reaches a minimum pressure and holds
there for at least 10 minutes.
- A rate of rise test of the cryopump vacuum chamber
indicates dp/dt < 10 milliTorr/min.
- With the roughing port and gate valve both shut,
restart the cryopump (cold head and compressor, if
used). The first indication of a successful
regeneration will be a reduction in pressure in the
cryopump. Allow the cold head to operate until the
temperature gauge indicates that the cryopanel is less
than 20 Kelvin. Keep a log of time and temperature.
Record entries at least every half hour. The cryopump
should get cold within three hours.
- If the regeneration is successful, open the gate
valve. Observe the vacuum on the nearest penning
gauge. Verify that the vacuum in the chamber
improves, or at a minimum, does not rise.
- If the regeneration is not successful, call Powell
Barber at 574-8076.
5 Cable Changes for Switching Ion Source
Ensure all appropriate supplies are off!
- Turn off the Preaccelerator H.V. Supply Panel in the
Control Room.
- Run the Inflector Magnet current to zero.
- Flip the sign for designating which source is in use
on the Preaccelerator H.V. Supply Panel.
- Exchange the H.V. lead for the appropriate source at
the supply in the Tandem Vault. Be wary of the lead;
some voltage may still be present.
- Change the knife switch position located in the gray
box at the Switching Magnet in the Tandem Vault to the
position for the desired ion source.
- Flip the switch located on the back of the
Preaccelerator H.V. Supply Panel in the Control Room
for the interlock circuit for the ion source required.
- Inspect the slits after the Inflector Magnet for the
appropriate setting ( » 0.125").
6 Tuning Beam out of the SNICS Source
These instructions assume the correct cathode is installed and the necessary
hardware/cable changes for selecting an ion source has been made. Also
assumed is that the source has been turned down after a previous run
but not necessarily to the idle mode.
Do not inject more than 10 microamperes of beam into the accelerator
under any circumstances.
- Open the source exit valve in the Tandem Vault.
- Insert the L.E. faraday cup and depress the
corresponding push button on the integrator panel.
Select the most sensitive scale on the integrator
initially and then adjust the scale if and when the
beam current pegs the meter.
- In the Control Room, turn the ion source deflectors to
zero.
- Turn on and bring up the Preaccelerator High Voltage
Supply to 120 KV.
- Adjust the inflector magnet supply to indicate the
predicted setting for the negative ion that is to be
injected into the Tandem. A table is provided on the
inflector control panel.
- If the beam has been run before and the source
parameters are known, adjust the SNICS Cathode and
Extractor supplies to those values at the High Voltage
Cage out in the Tandem Vault. If the Ionizer heater
is to be adjusted do it in 4 ampere steps separated by
4 minute intervals.
- If no parameters have been recorded or cannot be found
set the SNICS Cathode and Extractor supplies to 7.5 KV.
- Beam should be present on the L.E. cup, if not, adjust
the inflector magnet slightly and attempt to find and
maximize beam current. The inflector magnet should
not be more than 0.15 units off of the predicted
setting.
- An iterative approach is used to maximize beam on the
L.E. cup. After the magnet is fine tuned, adjust the
the SNICS Cathode and Extractor supplies in the Tandem
Vault to maximize beam current. When satisfied, again
adjust the inflector magnet in the Control Room and
then the source H.V. supplies again. After this
second round of tuning use the source deflectors in
the Control Room to increase beam current on the L.E.
cup. More rounds of adjustments should be attempted,
however, maximum beam transmission through the Tandem
does not occur at the same settings as those for
maximum L.E. faraday cup beam current. Mostly the
source deflectors and the inflector magnet require
slight readjustment when tuning through the Tandem.
- Assuming all the focusing and deflector elements are
maximized for beam current, one can only adjust the
Ionizer heater and the boiler temperature to attain
more beam form the source. First increase the Ionizer
heater current to increase the beam current,
do not exceed 290 watts or premature failure of the heater
will occur. If there is still insufficient beam
current, increase the cesium boiler temperature in
100° steps separated by 45 minute intervals.
Do not exceed 490° or the cesium vapor
will cause internal arcing in the source. If there is too much beam,
reduce the boiler temperature and monitor the beam
current. If less beam is still desired reduce the
Ionizer heater current in one ampere steps until the
desired current is reached. The beam is ready for
injection.
- Should one not have sucsess with tuning the desired
beam, reducing the ion source deflectors to 50% of the
optimum for a couple of iterations of source voltages
and inflector magnet adjustments might be a useful
approach. Ultimately, the deflectors should be
adjusted to give the maximum beam on target
7 Typical Cathode Behavior
Most often the material packed into the SNICS cathodes is either a solid
or powder. In general new, unused cathodes are often found to require
more time to reach the output level of cathodes that have seen previous
use. The nature of the material and how it was stored, particularly if
it is a hygroscopic or deliquescent, can be of paramount importance when
investigating a low negative ion output. Most powdered cathodes are pressed
here in the lab and are inherently ``gassy" due to voids in the pressed
material. The solid material cathodes are the preferred cathode whenever
possible. To reduce ``damage" to the cathodes while they are not in use
it is imperative that the cathodes be wrapped tightly in aluminum foil
and placed in a tightly capped bottle that has been back filled with argon.
Solid cathodes when initially inserted into the source, assuming it
is suitable material (ice cubes don't work well), will outgass in a very
short period of time. Beam from the ion source can typically be had in
sufficient quantity in the time it takes the ionizer and boiler temperatures
to be brought to the typical operating values.
Powder cathodes work best when they are pressed with dry powder and
stored in a dry environment. These cathodes will take longer to outgass
than their solid
counterparts and the ion source extractor and cathode voltages will often
suffer stability problems. Previously used cathodes, especially depending
on the nature of the material, can sometimes take up to half a day to
behave in a stable fashion and produce the desired beam current.
8 SNICS Temporary Turn Down
When a break or interruption occurs during the process of data collection
and the use of the negative ion source will not be required
by the experimental group for four or more hours it is desirable to turn
down the source to prolong its operational life time.
- Turn down and off the preaccelerator high voltage
supply in the Control Room.
- In the Tandem Vault, close the source exit valve.
- Reduce the Cesium Boiler Heater to zero on the variac
scale by turning the control rod located at the high
voltage cage.
- Reduce the ionizer heater current in four ampere steps
separated by two minute intervals to fifteen amperes
by turning the control rod attached to the ionizer
power supply located at the high voltage cage.
- Note in the Tandem Log Book, located in the Control
Room, the time the source was turned down to the idle
mode.
9 SNICS Turn Down to Idle Mode
When the use of the negative ion source is no longer required
by the experimental group it is desirable to leave
the source in a state to prolong its operational life time:
idle mode.
- Turn down and off the preaccelerator high voltage
supply in the Control Room.
- Turn down and off the source deflectors in the Control
Room.
- Turn the inflecter magnet supply completely down.
- In the Tandem Vault, close the source exit valve.
- Reduce the Cesium Boiler Heater to zero on the variac
scale by turning the control rod located at the high
voltage cage.
- Reduce the ionizer heater current in four ampere steps
separated by two minute intervals to fifteen amperes
by turning the control rod attached to the ionizer
power supply located at the high voltage cage.
- Turn the Lens, Extractor and Cathode H.V. supplies to
zero with the control rod extending from the H.V.
cage.
- Note in the Tandem Log Book, located in the Control
Room, the time the source was turned down to the idle
mode.
10 SNICS Cathode Change Instructions
Before beginning the cathode change procedure ensure the current settings
for the source parameters are recorded in the Cathode Utilization Log hanging
on the Source H.V. Cage. This procedure assumes the SNICS (Source of Negative
Ions by Cesium Sputtering) is in operation. The cage surrounding the SNICS
source is referred to as the ``Source H.V. cage" and the cage surrounding
the power supplies as simply the ``H.V. cage".
- In the Control Room, turn down the Preaccelerator H.V.
supply and then turn the power off.
- In the Tandem Vault source area, close the source exit
valve; observe that the H.V. warning beacon is not
rotating.
- Reduce the ionizer heater current in four ampere
steps separated by intervals of two minutes until
fifteen amperes is reached. This can be accomplished
by turning the supply control rod sticking through the
H.V. cage door; heater current is indicated by the
supply. Also, turn down the extractor voltage and
cathode voltage supplies by turning the appropriate
control rods at the cage door; output voltages are
indicated by the supplies.
- At the source vacuum control panel are two toggle
switches that must be placed in the ``unprot" position;
this is to prevent the isolation transformer from
shutting off supplies due to a vacuum excursion in the
source. Note the current vacuum indication at the
backing line thermocouple controller on the source
vacuum panel. Depress the red push button next to
the baffle switch while making the change.
- Open the source H.V. cage by releasing the two latches
located at the right edge of the door: pull on the the
latch handle until it rotates 90 degrees towards you
and then turn the latch handle until it clears the
fixed cage frame. The cage door is a bifold type and
should be opened by pushing it to the left.
- Investigate the H.V. cage to ensure the ionizer heater
supply and the Cesium feed line, indicated by a lit
power switch have not been interrupted.
- Using the shorting rod that is hanging on the cage at
the S.S. U-bolt, touch the source on each side of the
endmost ceramic insulator to reference the S.S.
(stainless steel) elements to ground. Hang the
shorting rod between the air lock VAT valve and the
HPS vacuum fitting clamp. * BE WARY OF THE WHITE
IONIZER HEATER LEADS AND THE BOILER FEED TUBE AS THEY
ARE LIVE*
- Remove the H.V. cathode lead from the stop clamp
(aluminum bar) attached to the cathode S.S. coolant
tube.
- Ensure the compression fitting sealing the cathode
assembly is only finger tight and then withdraw the
assembly slowly and carefully. At 5 3/4" of travel a
scribed line on the S.S. tubing will emerge from the
compression fitting. A 1/4" later a second scribed
line will emerge indicating that clearance has been
afforded the VAT air lock valve and it can be closed.
To close the valve rotate the black handle clockwise
(up and to the right) until it comes to a stop.
- The green knob on the Nupro valve can now be opened to
let the cathode air lock region up to atmospheric
pressure.
- Use one hand to withdraw the probe assembly (cooling
lines still attached) until it is free from the
source. With a glove on the other hand remove
(unscrew) the old cathode and replace it with the new
one.
- Install the cathode assembly back into the compression
fitting; loosen the fitting if necessary to get the
probe started and then tighten it finger tight again.
Slide the assembly in until the first scribed line is
even with the compression fitting.
- A nylon roughing line with a S.S. tube fitted to its
end should be at the source bottom cage grating,
ensure its free of debris and insert it into the Nupro
valves compression fitting. Snug the fitting on the
tube and ensure the valve is still open.
- At the source vacuum control panel, shut the backing
valve by putting its toggle switch in the manual close
position.
- On the backing line of the source diffusion pump is a
right angle, 1/4" brass valve with a black toggle
handle, open this valve to allow the cathode air lock
region to be roughed out. The vacuum can be monitored
at the backing line thermocouple controller on the
source vacuum panel. When the vacuum has reached the
reading previously noted (about 10 microns) close the
green handled Nupro valve and then the brass valve on
the backing line.
- Vacuum permitting, open the backing line valve with
the toggle switch at the source vacuum control panel
and place the two toggle switches in step 4 back to
the ``prot" position. Depress the red push button next
to the baffle switch while making the change.
- Remove the nylon roughing line from the Nupro valve
and place it back at the bottom cage grating.
- While watching the sputter source penning gauge, open
the VAT air lock valve by rotating the black handle
counter clockwise (up and to the left) until it comes
to a stop. A temporary degradation of the vacuum
should be indicated by the penning gauge. If the
vacuum does not show signs of recovering in 10 seconds
close the air lock valve and determine the source of
the gas load. Outgassing of the cathode is not
uncommon and is indicated by a vacuum that quickly
recovers but not to the level previous to the air lock
valve being opened. The vacuum will slowly improve
and attain the expected base vacuum of about 1 ×10-7
torr.)
- Carefully slide the cathode assembly into the source
until the aluminum stop clamp on the assembly is flush
with the compression fitting. There may be an
premature stop encountered before the stop clamp is
flush with the compression fitting, if so, slightly
wiggle the cathode assembly until it is free to be
fully installed. Ensure the compression fitting is
snug when the installation is complete.
- Reconnect the clear lead for the cathode H.V. supply
back to the stop clamp.
- Remove the shorting rod from the source and hang it
back on the cage at the S.S. U-bolt. Close the cage
door and remake the latches.
- Inspect the H.V. cage to ensure the extractor and lens
supplies are again energized. The cathode supply must
be reset by inserting a nonconducting rod (PVC or
nylon) through the cage and depressing the green
square button near the left edge of the supply front
panel.
- Increase the Ionizer current in four ampere steps
separated by intervals of five minutes until the
desired operating current is achieved (normally 23
amps).
- The cathode change is now completed. The source exit
valve can be reopened and the preaccelerator brought
back to voltage after the source vacuum has recovered
to » 1 ×10-6 torr. The inflecter magnet and source
supplies can now be tuned for the desired ion and beam
current on the L.E. cup.
11 Outgassing a New Ionizer
*******DO NOT RUN THE IONIZER OVER 290 WATTS*********
- Since the source has just been rebuilt it will need to be pumped on
for at least three hours. After this time the vacuum should be in the
low 10-6 torr range if there is no leak. Note in the logbook
the the source vacuum indication previous to outgassing the the ionizer
filament. If the vacuum has not reached this level in five hours a leak
may be present and it will have to be corrected prior to heating the ion
source filament.
- The ionizer is typically left with a small current flowing through the
ionizer after the rebuild just to ensure continuity. Assuming the vacuum
has recovered, increase the ionizer current in three ampere steps every
thirty minutes. If the vacuum has degraded to over 5×10-6 torr
due to a previous current increase, hold off on subsequent increases.
When the vacuum has returned to 5 ×10-6 torr or less begin the
three ampere increases again.
- When the Ionizer filament power is up to 290 watts for 30 minutes and
the vacuum has improved to better than 5 ×10-6, begin looking
for beam on the L.E. cup. The lab guide has instructions for tuning beam
out of the source. Instabilities in the Cathode and Extractor high
voltage elements will cause the beam current to be erratic and can
be an indication of poor vacuum in the ionizer region. The
voltage instability also appears on the high voltage supply meter indications
in the source high voltage cage. Patience or a reduction in the filament
power level, if beam current requirements allow, should correct this problem.
Regardless, reduce the ionizer temperature if possible to prolong its
operational lifetime.
12 Ion Source Shutdown and Disassembly
- In the Control Room, ensure the L.E. Faraday Cup is in
and the preaccelerator is switched off. Turn down and
off the Source Deflectors.
- In the Tandem Vault, close the source exit valve.
- Reduce the Cesium Boiler Heater to zero on the variac
scale by turning the control rod located at the high
voltage cage.
- Reduce the Ionizer Heater current to zero amperes in
four ampere steps separated by two minute intervals by
turning the control rod attached to the Ionizer Heater
power supply located at the High Voltage Cage.
- Leave the source to cool for an hour and thirty
minutes then turn the cooling water off.
- Turn off the Cesium Feed Line Heater by depressing the
illuminated power button with an insulated rod.
- Turn down the Extractor and Cathode H.V. supplies by
turning the control rods attached to each power supply
at the High Voltage Cage.
- Reduce the einzel lens voltage to zero by depressing
the labeled rocker switch at the H.V. cage control
panel. Turn the key switch at the panel to turned off
the isolation transformer providing platform power to
the H.V. cage. Both the Source and H.V. Cages may now
be opened.
- Using the shorting rod that is hanging on the cage at
the S.S. U-bolt, touch the source on each side of the
endmost ceramic insulator to reference the S.S.
(stainless steel) elements to ground. Hang the
shorting rod between the air lock VAT valve and the
HPS vacuum fitting clamp.
- Access to the external source body in now possible.
If breaking vacuum is necessary for work to proceed
then continue with this list. If the source is to be let up
to Argon, proceed.
- Turn off the cold cathode vacuum gauge. Verify that
the source exit valve is closed.
- Close the diffusion pump gate valve. The source may
now be back filled to atmospheric pressure with argon:
open the cylinder valve and adjust the regulator for
10 psi, open the flow gauge valve several turns, open
the valve attached to the source vacuum box, adjust
the flow to 10 L/min. Allow the gas to flow into the
source box until the pressure relief valve on top of
the source vacuum box indicates excess flow. Close
the valves associated with letting up the source.
- After five minutes feel the end flange of the source
to see if it is warm, if it is warm allow the source
to sit until it is cool to the touch.
- The cesium boiler assembly may now be dismantled so
that the cesium reservoir can be removed. Be very
careful when removing the reservoir because some
Cesium vapor may have condensed around the VCR
gaskets. The NEC ``Cesium Saver'' may be used to protect
the cesium from contamination; If needed, its use is
described in the the NEC Instruction manual.
- Remove the H.V. cathode lead from the stop clamp
aluminum bar attached to the cathode assembly.
- Ensure the compression fitting sealing the cathode
assembly is only finger tight and then withdraw the
assembly.
- Access to the source inner components is obtained by
removal of the electrical connections, the cathode air
lock valves and quick connect seals and the end most
12 hole flange. Be careful on removing the flange so
that damage is not done to the parts mounted on the
inside surface.
- When the source work is finished and it has been
reassembled, the source can be roughed out by turning
on the roughing pump at the fuse box mounted beneath
the H.V. cage by the mechanical pump which connects to
the source vacuum box by PVC piping. Open the ball
valve between the source box and the pump. Close it
at a source vacuum of 300 millitorr. Shutdown the
roughing pump and let the roughing line up to air with
the valve mounted on the PVC near the pump
- Place the backing and baffle valves in the ``unprot"
mode and open the baffle valve. When the vacuums are
below the set points for the respective controllers,
place the backing and baffle valves back to the
``protect" mode.
- Reconnect the electrical leads removed from the
source, install a cathode and close the source cage.
- Vacuum permitting, the source is ready to be brought
back to operating voltage, current and temperature
13 RF Source Operation
13.1 Operating principle
Helium is admitted into a quartz tube at a few mtorr where it is ionized
to He+ in an RF discharge. The ions are extracted through a tantalum exit
canal by applying a 4 kV positive bias to the anode at the other end of
the tube. Most of the anode bias potential is dropped across a small region
near the exit canal and the field lines have the effect of focusing and
accelerating the ions through the canal. The ions emerge with an energy
close to the anode potential. A large coil around the quartz tube produces
a magnetic field which improves the coupling of RF power into the discharge.
The He+ ion beam from the exit canal is focused by a gridded einzel lens
working in accel-decel mode with a bias of about -4.5kV to form a waist
at the Cesium vapor charge exchange cell. About 1% of the He+ entering
the CEC should get converted to He- in the 1s2s2p 4P5/2 metastable state.
The negative ion lifetime of approximately 0.5ms is sufficient to reach
the Tandem terminal stripper foil.
13.2 RF Discharge Contaminants
Because oxygen and other species form negative ions with efficiencies
much higher than helium the He+ beam is only a fraction of the total positive
beam, hence the He- beam is a small fraction of the negative beam. The
admitted helium and desorbed gases from the rf source bottle and boron
nitride exit canal insulator are some sources of the contaminant beams.
For optimum performance it is essential that the Rf source bottle assembly
be leak tight, that the helium used be greater than 99.99% pure, and that
all He tube and fittings be clean. In addition, it is also important to
operate the RF discharge with the helium flowing for 1 or more days prior
to the accelerator beam time to allow some of the contaminants to dissipate.
13.3 Summary of operation
- Check that the setup procedures have been properly
carried out. In particular ensure that the anode HV
supply (OPPLIS PMT supply) has been disconnected from
the PMT and has been set to the positive polarity.
- Turn on the ENI blue RF amplifier and power supply for
the 114 MHz oscillator. Set the attenuator between
the oscillator and amplifier to 10db; the output will
be more than 30W.
- Open the valve on the red helium bottle. Open the
helium leak until the discharge starts. Close it
until the discharge is no longer pink and has become
blue. The spherical deflector denoted Penning gauge
should only read a few x 10-6 torr.
- Turn on the anode high voltage and set to +4 kV. (To
use the program set the remote/manual switch at the
back to remote).
- Turn on the einzel lens supply. Set to 4.5 kV using
the program.
- Insert cup-1 em (use the control program) and optimize
the positive current by varying the gas pressure.
- Turn on the magnet supply (HP power supply). Optimize
the positive current with respect to magnet current.
Note: There are strange ``hysteresis'' type effects in
the discharge. The magnet current which was previously
``optimum'' is often not the optimum on a subsequent
optimization attempt.
- Focus the positive beam onto cup-2 using the einzel
lens ``focus", Q1 and the deflectors.
- Analyze for He+ using the Wien filter:
- Set WF electrostatic to 160V.
- Step the WF magnet current up from zero and monitor
cup-2 current. He+ should occur at about 265mA.
If the source has not been run recently 300 nA of
analyzed He+ on cup-2 is typical.
- Continue scanning to 1000mA and look for other
strong peaks.
It has been found that better transmission can be
obtained by operating at reduced Wien voltage, and
correspondingly reduced Wien magnetic field.
- To allow some of the contaminants to dissipate
operate the RF discharge with the helium flowing for 1
or more days prior to the accelerator beam time.
After this purge period the analyzed He+ beam on cup-
2, after optimizing the focusing, should be more than
+5 microamperes. If it is not, try adjusting the gas
leak and magnet current. Adjustment of the gas,
however, may be frustrating: increasing the flow
usually increases He+ output temporarily, followed by
a decrease and vice versa.
- Increase the cesium charge exchange canal middle tube
section temperature setting to 150 C.
- Monitor the temperature rise. At about 100 C the
positive current reading on cup-2 should start to
fall; at about 135 C the current should pass through
zero. The beam collected will consist of contaminant
species and ions rendered neutral by the charge
exchange canal some of which will pass undeterred by
the Wein filter to cup-2. The beam current indication
therefore is not due to helium alone and can be
misleading as demonstrated by the reading becoming
positive when the source platform is raised to high
voltage. At 150 C you should see on the order of -
50nA at cup-2.
- Close the source cage, and follow the instructions for
Changing Ion Sources in this lab guide. Check for
isolation of the platform from ground and nearby
objects.
- Raise the preaccelerator voltage to 80kV.
- Look for beam on the LE-cup and the source scanner.
There should be a beam on the scanner which does not
respond to the inflector magnet or the deflectors, and
superimposed, a beam which does. The non-responsive
beam is the neutral helium and contaminants, the
responsive beam is the negative He and contaminants.
- Inject the beam into the tandem and analyze on BS-1 or
BS-2. Carefully check the NMR reading and terminal
voltage (allowing for the offset in the GVM reading)
to ensure that it is He++ which is being analyzed.
16O 6+ can be transmitted with the same NMR setting
for He if the terminal potential is roughly 200kV over
the required setting.
- Using the program and other controls, optimize the He
current on the beam stop. A current of 50 to 100 na
on the beam stop should be expected.
Another set of instructions is contained in the file helisop.hlp. To
obtain a printout, exit the OPPLIS control software, hook up a printer
and type: print helisop.hlp (return).
14 RF Source Tuning Instructions with the PC
14.1 Focusing and Steering Control
Use the arrow keys to move the highlighted rectangle to the ``device"
column and then to the specific element in that column you wish to adjust.
After the particular lens or deflector is highlighted use the right arrow
key to move to the ``setnow" column and press the ``F" key. Tuning of the
the chosen device is done by pressing the up and down arrow keys to arrive
at the optimum setting. Using the left arrow to return the highlighted
rectangle to the ``device" column will set the devices operating parameters.
14.2 Optimizing on Source Cup-2
Press the ``N" key to allow beam current to be measured at cup-2; the
current is displayed at the lower center of the control screen. If the
output is less than 100 nanoampers of negative beam follow the ``A" set
of instructions below. If the current is 100 nanoamperes of negative beam
or greater the source is operating well and one should follow the
``B" instructions.
A) Press the ``P" key and observe the beam current on
cup-1. It should be 40 to 80 microamperes of
positive beam. If the reading is less, adjustment
of the discharge gas pressure is necessary. Due to
the location for gas adjustment it is not
physically possible to monitor the effect of the
pressure change at the computer screen so a digital
volt meter must be connected to the coax cable
labeled ``cup-1" near the flow control valve to
measure changes in beam current. Open the Helium
gas flow control valve at the RF discharge tube
inlet in steps no greater than a 12 degree
turn of the control rod; the effect should be noticeable
within seconds. If the beam output doesn't reach
40 microamperes seek assistance from either Brian
Schmidt or Ed Myers. When the cup-1 beam current
has reached 40 to 80 microampers remove the cup
from the beam path and adjust the Wein Filter
electrostatic voltage while monitoring current at
source cup-2. If the current still is not -100
nanoamperes check the status of the light blue
vacuum protection panel located in the source cage:
if the red light is on simultaneously press the two
reset buttons on the panel. If the vacuum
protection panel has not tripped and beam output
hasn't reach 100 nanoamperes of negative beam at
cup-2 seek assistance from either Brian Schmidt or
Ed Myers. When adequate beam is attained at cup-2
follow instructions ``B".
B) The current on the LE cup should be 50-100% of
source cup-2. If it is less than this, the source
needs some additional tuning. Press the ``E" key
and then try to small adjustments of the Wein
filter electrostatic voltage while observing beam
either at the LE cup or the HE tandem cup-1.
Increases in beam transmission may also be found by
fine tuning the source exit deflectors (rack
mounted in the control room above the PC screen),
quadrupole-2 (adjusted with the computer software)
and the inflector zero supply (located in the
control room above rack ``G").
Typical Beam Currents:
Source Cup-1 = 40-80 microamperes positive
Source Cup-2, With the Preaccelerator Off
= 100-150 nanoampers negative
Tandem L.E. Cup= 100 nanoamperes negative
Tandem H.E. Cup= 50-100 nanoamperes positive
15 This page for Polarized Lithium Stuff
16 Hardware/Cable Changes for Switching Target Rooms
16.1 From the Tandem Target Room to the LINAC Target Room
Ensure all appropriate supplies are off!
- The Slit Stabilization Amplifier is shared between the
Tandem and LINAC 90° magnets. Unplug the 110 volt
power cord and disconnect the output signal cable D-
type connector from the amplifier and terminate it at
the LINAC Slits Connector Box. Detach the two coax
cables from the image slits and move the amplifier to
the LINAC 90° magnet image slits. Connect the coax
cables to the image slits; ensure that the H.E. and
L.E. slits are coupled to the correct amplifier
inputs. Connect the Cannon connector to the slit
amplifier; it should be laying in the vicinity of the
image slits. Plug the 110 volt power cord into a
receptacle.
- Check the external second stripper in the LINAC hall
for the presence of a foil in the beam path and the
condition of the foil if stripping to a higher charge
state is required.
- Open each Tandem 90° magnet object slit to 0.2" on
both the horizontal and vertical pairs.
- The switching magnet in the Tandem Target Room uses
the same power supply as the magnet which serves the
LINAC Target Room. Ensure the supply is turned off in
the Control Room. The power supply and the enclosure
housing the beam routing knife switches are located in
the Tandem Vault, in the rack to the North of the H.E.
entrance. The output of the supply is switched to the
Tandem Target Room switching magnet with the top knife
switch and the polarity for the correct beam
deflection with the bottom.
- Ensure both the LINAC 90° and switching magnets have
cooling water (cooling lines should be cool to the
touch).
- Close the Tandem Target Room switching magnet beamline
valve. Ensure the vacuum in the Tandem 90° magnet,
H.E. beam line and LINAC line are below 1 ×10-5 torr.
If this is so, open the hand valve before the 90°
magnet and the LINAC line pneumatic valve.
- To degauss the old 90° magnet rundown the current at
the control panel, change the deflection for the
reverse mode, increase the magnet current a few amps,
then back down and return to the normal deflection
mode.
- In the Control Room, exchange the input connector for
the Gauss Meter from the one for the Tandem to that
labeled for the LINAC.
- Control of deflectors D-1, D-2, QIII-A and QIII-B is
obtained by dropping the switch at the bottom of rack
F to the position labeled LINAC. Ensure the
appropriate supplies are off before making the switch.
- The beam chopper for the LINAC should have the
amplifier turned on in the Tandem Vault, Southwest of
the Tandem Target Room 90° magnet. Ensure the drive
signal for the amplifier in the Control Room LINAC
electronics rack is unplugged when first tuning beam.
- Turn around the sign on the LINAC Hall entrance door
to indicate the presence of beam and then secure the
door so that entry can only be made via the control
room. Close the gate separating the Tandem target
room from the LINAC Target Room.
16.2 From LINAC Target Room to Tandem Target Room
Ensure all appropriate supplies are off!
- The Slit Stabilization Amplifier is shared between the
Tandem and LINAC 90° magnets. Unplug the 110 volt
power cord. Remove the amplifier output signal cable
multi-pin Cannon connector and lay it down in the
cable tray. Detach the two coax cables from the image
slits and move the amplifier to the Tandem 90° magnet
image slits. Connect the coax cables to the image
slits; ensure that the H.E. and L.E. slits are coupled
to the correct amplifier inputs. Remove the Cannon
connector from the LINAC Slits Connector Box and
connect it to the slit amplifier box. Plug the 110
volt power cord into a receptacle.
- Close each horizontal object slit to 0.115" on the
Tandem 90° magnet. Open the vertical object slits all
the way.
- The beam chopper for the LINAC should have the
amplifier turned off in the Tandem Vault, Southwest of
the Tandem Target Room 90° magnet.
- The switching magnet in the Tandem Target Room uses
the same power supply as the magnet which serves the
LINAC Target Room. Ensure the supply is turned off in
the Control Room. The power supply and the enclosure
housing the beam routing knife switches are located in
the Tandem Vault, in the rack to the North of the H.E.
entrance. The output of the supply is switched to the
Tandem Target Room switching magnet with the top knife
switch and the polarity for the correct beam
deflection with the bottom.
- Ensure that both Tandem 90° and switching magnets have
cooling water (cooling lines should be cool to the
touch).
- Close the LINAC beam line pneumatic valve. Ensure the
vacuum in the Tandem 90° magnet, H.E. beamline and
switching magnet are below 1 ×10-5 torr. If this is so,
open the hand valve before the 90° magnet and the
switching magnet pneumatic valve.
- In the Control Room, exchange the input connector for
the gauss meter from that for the LINAC to that
labeled for the Tandem. Ensure the Tandem 90° magnet
is in the correct deflection mode. If not turn supply
down before making the switch.
- Control of deflectors D-1, D-2, QIII-A and QIII-B is
obtained by raising the switch at the bottom of panel
F to the position labeled Tandem. Ensure the
appropriate supplies are off.
- Close the gate between the two Target Rooms. Rope off
the passage between the Tandem Vault and the LINAC
Hall.
17 Hardware/Cable Changes for Choosing a BeamLine out of
the Switching Magnets
17.1 LINAC Target Room Switching Magnet
Ensure all appropriate supplies are off!
- The switching magnet in the LINAC Target Room uses
the same power supply as the magnet which serves the
Tandem Target Room. Ensure the supply is turned down
in the Control Room. The power supply and the
enclosure housing the beam routing knife switches are
located in the Tandem Vault, in the rack to the North
of the H.E. entrance. The output of the supply is
switched to the Linac Target Room switching magnet
with the top knife switch and the polarity for the
correct beam deflection with the bottom.
- Move the power cable for Q-4 to the appropriate
experimenter's quadrupole in the LINAC Target Room.
- Control of the deflector D6 and measurement of beam
current by Faraday Cup no.6 on the experimenter's beam
line is enabled by making the correct connections at
the labeled patch panel on the LINAC switching
magnet support stand. Beam current measurements
provided for in the experimenter's chamber can be made
by making the correct connection to TC-2 at the
switching magnet patch panel; this panel faces West
below the magnet.
- Move the roving Faraday cup controller to the
experimenter's beamline and connect the controller
cable at the cup.
17.2 Tandem Target Room Switching Magnet
Ensure all appropriate supplies are off!
- The switching magnet in the Tandem Target Room uses
the same power supply as the magnet which serves the
LINAC Target Room. Ensure the supply is turned down
in the Control Room. The power supply and the
enclosure housing the beam routing knife switches are
located in the Tandem Vault, in the rack to the North
of the H.E. entrance. The output of the supply is
switched to the Tandem Target Room switching magnet
with the top knife switch and the polarity for the
correct beam deflection with the bottom.
- The beam current is measured on beam dumps for each
individual beam line. Connection to the current
integrator in the Control Room is made locally with a
coax cable terminated with an alligaytor clip.
- The beamline deflector, as of this writing, is
physically dedicated to a beam line and must be moved
to a new beam line with the help of a few hand tools.
- The Quadrupole power supply is located in the Tandem
Target Room next to the Tandem Vault shield door. The
out put of the supply is switched to the new beam line
at the quadrupole. Move the lead to the new
quadrupole and plug it in.
18 Tandem Beamline SF6 Gas Security Ball Valves
Each beam line exiting the Tandem has a large diameter, pneumatically
actuated Worcester Controls ball valve that will automatically close under
normal operating conditions if a pressure rise on the order of in. of Hg
is detected on the Tandem side of the valve. Because the Tandem is filled
with SF6 at 85 psi and the accelerator tubes and beamline are
under vacuum a failure of an O-ring seal, accelerator tube metal to glass
bond or any major compromise of vacuum integrity within the machine could
have catastrophic results. The intention of the valves are two fold.
One is to contain the gas to prevent its loss, a $70,000 investment. The
other is to prevent damage to the equipment on the beam line that is designed
to withstand the implosive forces of vacuum and not the explosive 85 psi
tank pressure.
An Edwards High Vacuum Ltd. pressure switch is located on the L.E. end
of the Tandem beam line to sense the fault condition along with a 30 in.
Hg to 60 psi compound gauge to monitor the tube vacuum/pressure in the
range where penning gauges and thermocouples are not usable. The control
panel is in the vault L.E. electronics rack below the beamline, and the
key switch for disabling control of the ball valves is kept in the red
case underneath the Control Room console. When the vault control panel
is in the unprotected key switch position the ball valves can be opened
and closed at will. In the protect position the ball valves can only be
opened when the beamline pressure switch is closed. An LED on the control
panel, labeled sensor contact, will illuminate when the switch is closed.
The Gas Security Ball valve controller is integrated with the Tandem
Pelletron interlock circuit. A closure of the ball valve either manually
or due to a failure of the vacuum integrity is sensed by the Ball valve
controller and results in the Pelletron charging supplies being interrupted
via the interlock panel.
Because they are pneumatically controlled, a loss in compressed air
service will result in the valves closing. There will be no electric circuit
indication such as the sensor contact LED being off or the Pelletron H.V.
supplies being tripped off. If beam transmission through the machine is
nil, investigating the ball valves themselves will allow ascertaining the
valves state. On top of the pneumatic actuators are square posts that
turn with the ball valve, the valves are open
if the small silver stud on one of the flats is facing West.
19 Tandem Beamline Vacuum Protection System
The logic and status chassis for the Tandem Vault beam lines is above
the switching magnet power supply, North of the H.E. vault shield door.
There is a status panel also in the Control Room above the beamline devices
panel. The L.E., H.E., Sputter Source and Polarized Source vacuum indications
are displayed in the Control Room also.
Each Tandem beamline fast valve has a dedicated control box and penning
gauge except for the 90° magnet which has a penning gauge but no fast
valve to control.
Each controller has a ``good vacuum" output signal that is ``anded" together
in the logic chassis with the other controllers. If any of the five penning
gauge controllers detect a vacuum incident, all four of the fast valves
will close and the Tandem Pelletron charging H.V. supplies will be disabled.
The Tank Gas Security Ball Valve Controller is also ``anded" with the
beamline penning gauge controllers in the logic chassis and an LED indication
for the ball valves status is provided. If either the L.E. or H.E. Gas
Security ball valve is closed, the Pelletron H.V. charging supplies are
disabled. If the ball valves have closed on there own something could
be severely wrong and a staff member familiar with this system should be
consulted before they are reopened. More information about the Gas Security
ball valves can be found through the table of contents.
The source penning gauge is not included in the ``anded" logic to close
the beamline valves. The source penning gauge will close the source exit
valve and turn off the preaccelerator H.V. supply if the ion source vacuum
sufficiently degrades. The valve control boxes for the two sources are
different, so, arbitrary interchanging of the boxes cannot be done.
The fast valve control box/penning gauge controllers themselves do have
many common features. The valve control boxes can be used to open and
close a valve at will in the unprotected mode (no vacuum consideration).
In the protected mode, the valve can only be opened if the vacuum
at the associated gauge head is better than the chosen set point,
approximately 5 ×10-6. A controller that has sensed
a vacuum excursion will have a flashing LED;
to rearm the protection circuit and open the valve(s) that has tripped
close, depress the push button reset switch on the front panel of that
controller, the LED should stop flashing. Be cautious with the beamline
valves: if all the controllers sense a good vacuum and all valve switches
are in the open position, all four fast valves will open
simultaneously. If this is not desired, place the valve control box switches
to close, reset the tripped penning gauge controller, and then open the
valves individually.
If a penning gauge controller is out of service or it is desirable to
prevent a controller from closing the beam
line valves, it can be overridden at the logic panel by
placing the switch indicated for that controller in the
override position. The Ball valves should only be overridden after a
staff member familiar with this system has been consulted.
20 Tandem Pelletron Interlock Panel
To prevent dangerous operation of or damage to the accelerator an interlock
circuit is employed. The status of the various interlock switches is displayed
at the interlock panel. The switches and their status are in a serial
configuration therefore should one interlock not be closed all others ``down
stream" will also indicate an open situation and the LEDs will be extinguished.
The panel layout is natural in that all the LEDs to the right of the offending
switch will be out; once that interlock is satisfied its LED will illuminate
and the rest to its right should also shine if the switches are closed.
The interlock circuit, depending upon which switch opens up, will either
turn off the charging supplies or both the charging supplies and the chain
drive motors. All the interlocks up to and including the tank pressure
switch will disable both the chain drives and power supplies, the remaining
only affect the charging supplies.
There are nine LEDs on the Tandem Pelletron Interlock Panel. A brief
description of each interlock or LED indication in the order that they
are appear on the panel follows.
Status Power: This lamp will be lit if the the power
switch key is turned to on and the
12V dc supply used for the series
circuit is present.
Control Power: This lamp indicates AC power is present
within the chassis when the switch key
is turned to on.
HE Tank Door: A push button switch is mounted on the
Tandem High Energy Tank Door to sense
when the door is fully rotated closed.
LE Tank Door: A push button switch is mounted on the
Tandem Low Energy Tank Door to sense
when the door is fully rotated closed.
LE Pendulum: A push button switch is mounted to the
LE drive sheave assembly to sense
excessive Pelletron chain stretch or
failure.
HE Pendulum: A push button switch is mounted to the
HE drive sheave assembly to sense
excessive Pelletron chain stretch or
failure.
Tank Pressure: A pressure switch is mounted to the
Tandem pressure vessel to ensure a
minimum pressure of 35 psi is
established before the the Pelletron
chain is started.
Vac Ball Valves: This interlock is closed when the
Tandem Beam Line Valve Protection
System detects no tripped penning gauge
controller or beamline SF6 protection
ball valve closure. A separate status
panel is present in the Control Room
for this beamline protection system and
an override/status panel is located in
the Tandem Vault to the North of the HE
door. A more detailed description of
that circuit can be located through the
Table of Contents.
TPS OV/UV: The Terminal Potential Stabilizer
supplies a relay that relaxes whenever
the terminal voltage varies beyond a
set percent of the value displayed at
the terminal voltage reference
potentiometer. This TPS feature must
be enabled to trip the interlock panel
for an out of range voltage excursion.
Should a condition arise where disabling the Tandem Pelletron Interlock
Panel is desired, such as a tank opening, an override switch is located
in the back of the panel chassis. It is accessible from behind the electronics
racks.
21 Terminal Potential Stabilizer
The Terminal Potential Stabilizer (TPS) consists of five main components:
Controller Unit, Generating Voltmeter (GVM), Analyzing Slits, Capacitive
Pick-Off Plates (CPO) and the Corona Probe.
The Controller as is suggested, controls the terminal voltage by comparing
signals from the GVM, slits and the CPO to produce a correction signal
that modulates the current flowing to the terminal from the corona probe.
The GVM is mounted on the tank wall of the Tandem opposite the terminal.
A four bladed rotor spins at 3450 rpm over a surface divided into eight
segments each the size of one blade. As the rotor spins it uncovers some
segments and exposes them to the terminal voltage which results the segment
charging to a voltage proportional to the terminal voltage. When the segment
is again shielded by the rotor, charge will drain away. The signal produced
by the GVM is conditioned locally by an amplifier and routed to the controller.
The analyzing slits are in the typical configuration, downstream of
the 90° analyzing magnet, parallel to the pole face plane and opposite
each other on the exiting beamline. They are adjustable with micrometer
style knobs for each and are electrically isolated. Beam being bent around
the 90° magnet impinges upon the slits creating a signal proportional
to the beam it senses. The signals from the slits are conditioned locally
by an amplifier and routed to the controller.
There are two CPO plates in the Tandem that are mounted on the tank
wall opposite the terminal. These plates are electrically isolated and
sense fluctuations of terminal voltage at frequencies above those detectable
by either the slits or the GVM. Two plates are used to cancel out physical
movement of the column that would be detected as a voltage fluctuation
by a single plate as the separation between the terminal and plate changes.
The signal from the CPO plates is conditioned locally by an amplifier and
routed to the controller.
The corona probe is also mounted on the tank wall opposite the terminal.
The probe is mounted on a shaft that can be driven to different distances
to the terminal depending on the terminal operating voltage. The end of
the probe consists of a shell with 12 needle points extending slightly
beyond the polished shell surface. The voltage on the needle points determines
the flow of electrons to the positively charged terminal. Modulating this
flow of electrons is done by the Controller based on the information provided
by the GVM, slits and the CPO.
The typical operation of the system is described to assist the operator
in understanding how the system maintains terminal stability. The description
is not intended to be used for bringing up the terminal voltage as it excludes
the Charging Controllers and positioning of the corona probe. Feedback
or modulation of the probe current will take place only when the TPS Control
Gain is turned up.
The Controller has three possible modes of operation namely GVM, Slit
or Auto. The Auto mode allows the TPS to switch into one of the other
two modes depending whether the terminal voltage is approximately 50 KV
off of the controller Terminal Voltage Reference Potentiometer setting
and/or beam current above 10 nanoamperes is sensed by the analyzing slits.
Typically the Controller is in the Auto mode.
With less than 10 nanoamperes of beam on the analyzing slits, the Tandem
will be in GVM mode. The correction signal in this mode is derived by
comparing the front panel Terminal Voltage Reference Potentiometer setting
to the GVM measurement of actual terminal voltage. The CPO signal is
added to this to produce the error signal that ultimately modulates the
corona probe voltage. The operating voltage
of the probe needles is proportional the Grid Bias indicated on the Controller
chassis. In this mode the terminal voltage will track
the Reference Potentiometer setting and allows one to scan the terminal
voltage until beam strikes the analyzing slits.
With beam on the slits and the GVM and Terminal Voltage Reference Potentiometer
in relative agreement the TPS Controller will switch to Slit mode. The
controller compares the current striking one slit to the other to create
an error signal that attempts to keep the measured current balanced. The
slit on the inside of the analyzing magnet bend is the Low Energy (LE)
slit and the one on the outside is the High Energy (HE) slit. If an excess
of beam is detected by the LE slit an error signal is produced by the TPS
that will reduce the probe electron current flowing to the terminal causing
the terminal voltage to rise which will bring more beam current to bear
on the HE slit until a balanced situation is again reached. Like the GVM
mode, the CPO signal is added to modulate the probe current. In this control
mode adjusting the Terminal Voltage Reference Potentiometer has no effect
until the disagreement with the GVM causes the TPS to revert to GVM mode.
When the TPS is in Slit mode the Reference Potentiometer should be adjusted
to agree with the GVM indication.
22 Operating Instructions for the Tandem Pelletron
22.1 To Turn the Tandem Pelletron On
- Set the TERMINAL POTENTIAL STABILIZER CONTROL MODE to AUTO
and turn the CONTROL GAIN and CPO GAIN to zero.
- Turn on the LOW ENERGY CHARGING CONTROLLER AND THE HIGH
ENERGY CHARGING CONTROLLER by turning their key switches CW to the
ON position. To start the charging chains lift the momentary CHAIN
switch to the ON position for each CONTROLLER. After approximately
ten seconds the lamp below the switch will illuminate indicating the chain
is up to speed.
- Set the corona probe BIAS CURRENT to 35 microamps on the TPS
- Set the corona probe to the approximate position indicated in the table
for the desired terminal potential.
- Set the GVM REFERENCE VOLTAGE knob to the correct voltage (e.g.
8 MV would be ``0800").
- Ensure the TERMINAL CHARGE POTENTIOMETER on the LOW ENERGY
CHARGING CONTROLLER is turned down to zero, CCW.
- Turn both POWER SUPPLY switches to ON on the CHARGING CONTROLLERS.
Their indicator lamps should glow.
- While watching the corona probe GRID voltage, carefully increase the
charge carried by the chains by turning the TERMINAL CHARGE POTENTIOMETER
CW. Turn the TERMINAL CHARGE POTENTIOMETER until the GVM/TV Balance
indicates approximately zero or the GRID voltage has reached -9V. If
at any time the GRID voltage reading goes beyond -1OV, run the corona
probe out to reduce it. Fine tune the corona probe position and the up-charge
so that the GRID voltage reads approximately -9V when the desired terminal
voltage is reached.
- Enable the OVER/UNDER VOLTAGE PROTECTION and set both the CONTROL
GAIN and CPO GAIN to 5.
- Readjust the corona probe if necessary to attain -9V; do not exceed
this voltage on the GRID.
- Set the 90° magnet to the appropriate field and put beam through
the Tandem. If the TPS does not switch to the SLIT CONTROL MODE and lockup
on a beam the GVM REFERENCE VOLTAGE knob can be adjusted slightly
to scan for the beam; only a slight adjustment should be necessary.
With beam on the slits, and the TPS in SLIT CONTROL MODE adjust
the TERMINAL CHARGE POTENTIOMETER so that the Slit Balance meter
reads zero, and retrim the corona probe position, if necessary, to get
-9V on the GRID.
- Adjust the GVM REFERENCE VOLTAGE knob so that the GVM/TV Balance
meter indicates approximately zero.
IF THERE IS A SPARK
The OVER/UNDER VOLTAGE PROTECTION interlock on the TERMINAL
POTENTIAL STABILIZER panel will be tripped and the red LED should be
lit. The CHARGE CONTROLLER POWER SUPPLIES are disabled by this protection
circuit, however, the chains will continue to run.
- Turn the CONTROL GAIN and CPO GAIN to zero
- On the LOW ENERGY CHARGING CONTROLLER turn the TERMINAL CHARGE
POTENTIOMETER back to zero.
- Reset the TPS OVER/UNDER VOLTAGE PROTECTION interlock by depressing
the momentary switch.
- Turn up the TERMINAL CHARGE POTENTIOMETER until the previous terminal
potential is reached; watch for signs of conditioning.
- Check that the GRID voltage reads approximately -9V .
- Set the CONTROL GAIN and CPO GAIN to 5.
- Put beam through the Tandem Pelletron and adjust the TERMINAL CHARGE
POTENTIOMETER to center the Slit Balance meter.
- Enable the OVER/UNDER VOLTAGE PROTECTION circuit.
22.2 TO TURN OFF THE Tandem PELLETRON
- Disable the TPS OVER/UNDER VOLTAGE PROTECTION and turn the
CONTROL GAIN and CPO GAIN to zero.
- Turn the CHARGE CONTROLLER TERMINAL CHARGE POTENTIOMETER back to
zero and turn off the CHARGING POWER SUPPLIES at the toggle switch.
Depress the momentary switch for the chains to turn them off and then turn
the panel key switch to off.
22.3 TO CHANGE THE TERMINAL POTENTIAL
- Disable the TPS OVER/UNDER VOLTAGE PROTECTION and turn the
CONTROL GAIN and CPO GAIN to zero.
- If the terminal potential is to be decreased, reduce
the CHARGE CONTROLLER TERMINAL CHARGE POTENTIOMETER until the TPS
displays the TERMINAL VOLTAGE desired. Typically the terminal voltage
will drop as the corona probe is run in requiring increases of chain current.
Adjust the corona probe position and the TERMINAL CHARGE POTENTIOMETER
to get approximately -9V on the GRID.
- If the terminal potential is to be increased, run the
corona probe out to the approximate position indicated in the table for
the desired terminal potential. While watching the corona probe GRID
voltage, carefully increase the CHARGE CONTROLLER TERMINAL CHARGE
POTENTIOMETER. Increase the TERMINAL CHARGE POTENTIOMETER until
the TPS displays the TERMINAL VOLTAGE desired or the GRID voltage
has reached -9V. If at any time the GRID voltage reading goes beyond
-1OV, run the corona probe out to reduce it. Readjust the corona probe
position and the TERMINAL CHARGE POTENTIOMETER so that the GRID
voltage reads approximately -9V at the desired terminal voltage.
- Adjust the GVM REFERENCE VOLTAGE knob so that the GVM/TV Balance
Meter indicates zero.
- Enable the TPS OVER/UNDER VOLTAGE PROTECTION and turn the
CONTROL GAIN and CPO GAIN to five.
- Readjust the corona probe if necessary to attain approximately -9V on
the GRID; do not to exceed this voltage.
- Set the 90° magnet to the appropriate field and put beam through
the Tandem Pelletron.
- If the TPS does not switch to the SLIT CONTROL MODE and lockup
on a beam the GVM REFERENCE VOLTAGE knob can be adjusted slightly
to scan for the beam; only a slight adjustment should be necessary.
- With beam on the slits, and the TPS in SLIT CONTROL MODE adjust
the TERMINAL CHARGE POTENTIOMETER so that the Slit Balance
meter reads zero; retrim the corona probe position, if necessary, to get
approximately -9V on the GRID.
- Adjust the GVM REFERENCE VOLTAGE knob so that the GVM/TV Balance
meter indicates approximately zero while the TPS is in SLIT CONTROL
MODE.
23 Extended Tandem Pelletron Shutdown
If the current experiment has concluded and machine downtime is expected,
the following list should be followed. Ensure a log sheet has been filled
out that includes all the beamline devices settings, Faraday cup currents,
Tandem parameters,...etc.
- Return beam to the L.E. Faraday cup.
- Turn the Terminal Potential Stabilizer Control and
CPO Gain to zero, Disable the over/under voltage
protection.
- Turn the Terminal Charge Potentiometer on the Low
Energy Charging Controller down to zero, CCW.
- Turn both power supply switches to off on the
Charging controllers.
- Stop the charging chains by depressing the
momentary chain switch to the off position for each
Controller.
- Turn off the Low Energy Charging Controller and the
High Energy Charging Controllers by turning their
key switches CW to the off position.
- Turn down the supplies for these devices.
- switching magnet
- 90° magnet
- Target room quadrupoles and deflectors
- accelerator quadrupoles and deflectors
- L.E. beamline lens 2.
- Close the hand valve before the Tandem 90° magnet.
- Follow the source turn down instructions.
- Remove control power key if a tank opening is
required.
24 Terminal Stripper Foil Changer
A change in terminal stripper foil is indicated by a decrease in beam
transmission through the Tandem. To change the foil one of the two rocker
switches on the foil changer panel in the Control Room should be depressed.
The direction of movement, either forward (increment) or reverse (decrement)
should be that which would bring a fresh foil into the beam path, consult
the logbook for used foil information. Motion of the foil band will continue
while a switch is pressed. When the direction of the foil change is reversed
a considerable amount of backlash, inherent with magnetic couplings, will
result in a longer period than for the initial foil change. Use the rocker
switches to maximize beam transmission through the Tandem.
The foil changer can be placed in an automatic change mode that allows
the foil to be incremented or decremented to a preset number. On the foil
changer panel is a thumb wheel numeric display that should be adjusted
to indicate the desired foil number. A small toggle switch is located
at the left corner of the display should be switched to the ``ena." (enable)
mode. The preset push button should be depressed, the labeled LED below
the display should light. Now depress the rocker switch that will allow
the foil changer to either increment or decrement to the chosen value.
Fine tuning of the foil will be required after the preset is reached.
When finished with the preset function put the toggle switch back to the
``dis." (disable) position
The equipment employed in the changing of the foils consist of the the
control panel in the Control Room, a slosyn motor, a shaft encoder, control
rod with coupling hardware to span the L.E. column and a magnetic coupling
to transfer motion to the stripper foil band which resides in vacuum.
Within the stripper foil housing are two bands of foils, 300 foils per
band for a total complement of 600 foils. A description of the band changer
can be found through the Table of Contents. The foils are rotated into
the beam path by the slosyn motor via a control rod spanning the L.E. column
and terminating in the terminal.
The 110 Vac slosyn motor is bidirectional and receives power
from the Control Room via the L.E. bulkhead feedthrough BU 9, pins No.
5,6 and 7 (Increment, decrement and AC neutral respectively). The 3000
count shaft encoder is used for record keeping of the foil inventory.
The encoder is coupled to the motor by a timing chain and a 10 to 1 reducing
gear. The encoder signal is transmitted to a four digit counter LED display
on the foil control panel via the L.E. bulkhead feedthrough BU 7, pins
No. 4,5,6,7,8 and 9.
25 Terminal Foil Band Changer
The terminal band changer is actuated in the Control Room at the foil
changer panel. A momentary three position switch is used along with a keyed
enable switch in hopes of removing the uncertainty of knowing which band
is in use and which band, if any, is exhausted. To adjust or change bands
insert the key into the ``Band Change Enable" slot and turn the key clockwise.
The key is kept in the red box below the console. Ensure you are aware
of what band is being used before making a change. Press and hold the
appropriate toggle switch until beam on the HE cup drops off and then returns.
Continue holding the switch and note the maximum beam current observed
before the beam begins to fade again. Release the switch when the beam
current begins to drop. Now fine tune the stripper foil by pressing the
switch to move back towards the previous band position; release the switch
when the previously observed maximum beam current returns to the HE cup.
When satisfied with the band position, ensure the correct LED band indication
is lit for the correct band by a short flip of the band changer switch.
Turn the key counter clockwise to disable the band changer mechanism.
This paragraph describes the details of the band changer mechanism.
The Foil/Band changer electrical leads run out to the L.E. Tandem base
plate and then internally via the bulk head feedthrough BU 9 on pins #2,
3 and 4. Inside the machine, behind the L.E. base plate aluminum cover,
is the slosyn motor that drives the control rod whenever the enable key
and momentary switch in the Control Room is closed. The control rod spans
the length of the L.E. column and terminates in the terminal; the control
rod is on the West side of the column and is above the accelerator tube.
The control rod rotates a cam/microswitch assembly in the terminal that
is capable of sensing the direction of rotation of the control rod.
The microswitches energize a timer/relay once per revolution of the control
rod ( » 3 seconds) which in turn powers the motor that either
lifts or lowers the end to the stripper foil housing for a preset interval.
Movement of the stripper foils is achieved by a gimbaled pivot point on
the housing allowing positioning of the foils at the beam end of the housing.
The travel or pivot arc of the housing is limited by another set of microswitches
that interrupts the band changer motor power when at the end of the adjustment
range.
26 LETTING ACCELERATOR TUBES UP TO DRY NITROGEN
These instructions are specifically written for letting up the minimum
beamline volume to gain access to the accelerator tubes and anything between
the HE fast valve and the LE Gas Security Ball Valve -typically for a foil
change. Puffs of gas or excessive gas flows must be avoided to protect
the fragile stripper foils in the terminal of the Tandem. If access to
additional beamline length is necessary more pumps may need to be isolated
and different valves closed.
- In the Control Room turn down the lens and
deflectors on the L.E. beam line.
- Turn off the L.E. Buncher amplifier in the vault.
- Turn power off to the L.E. and Cup 1 controllers
before letting up the beam line to dry Nitrogen.
Remove the lead from the L.E. cup that connects to
the 300 V dc suppression battery.
- Turn off the Low Energy and High Energy Penning
gauge controllers.
- Pump the beamline through the sputter source. Put
the SNICS source in the Idle mode (consult the
Table of Contents) and place the exit, baffle and
backing valves in the unprotected mode. Ensure the
source exit valve and the others are open.
- Close the Low Energy cryopump gate valve.
- Close the Low Energy Gas Security Ball Valve. With
the key kept under the console in the Control Room,
switch the valves at the vault control panel to the
unprotected position to prevent the High Energy
Ball Valve from automatically closing when letting
up the tubes. Additional information on the Ball
Valves can be located through the table of
contents.
- Close the H.E. fast valve to maintain a vacuum in
the down stream beamline. Ensure the hand valve
before the 90° magnet is open.
- Close the High Energy cryopump valve.
- Close the LINAC entrance valve to the North of the
Tandem 90° magnet.
- The valves and gauges necessary for letting up the
tubes are at the H.E. end where the beamline exits
the Tandem. A manifold with copper tubing is on
the East side of the beam line. Slowly open the
1/4" ball valve exiting the manifold and in series
with the 0-50 L/min Air flow gauge so that the
tubes can be let up to Nitrogen. Ensure the needle
valve at the Nitrogen flow gauge is closed. The
compound gauge should indicate vacuum when the
valve is opened.
- Adjust the flow gauge needle valve so that the
gauge at the inlet is at 29 in. of Hg and note the
flow rate; it should be about 25 L/min.
Periodically adjust the flow rate to maintain that
which was previously noted. The gas will need to
flow for » 1 hour to fill the void.
- When the tubes are at atmosphere or slightly above,
close the flow gauge valve and, if necessary,
slowly bleed off the excess pressure by slowly
opening the pump out port 1 1/4'' ball valve that is
attached to the copper manifold.
- Depending on the circumstances it may be preferable
to allow a small flow of Nitrogen to reduce the
quantity of air that will migrate into the tubes
while they are open. Open the flow gauge slightly
after the the beamline vacuum seal is broken.
27 Pumping down the Accelerator Tubes
After all the broken seals are remade the tubes are ready to be pumped
out. An oil free vacuum pumping system must be employed when pumping
down the tubes. Do not use an oil sealed mechanical pump as they can allow
oil mist to back flow into the accelerator tubes. A Carbon Vane pump followed
by a Sorption pump is sufficient. To protect the fragile foils, puffs
of gas or excessive gas flows must be avoided so use care. Open
valves slowly to begin the pumping.
- The port for pumping down the tubes is in series
with the 1 1/4" ball valve attached to the manifold
at the HE beamline. Attach the pumping station to
the end of the 1" copper pipe port and evacuate the
pipe up to the closed 1 1/4" ball valve. Slowly
begin opening this ball valve and stop as soon as
either the pumping station vacuum gauge indicates a
pressure rise or the vacuum pump audibly responds
to a gas load. Slowly open the ball valve more as
the vacuum continues to improve in the tubes. The
valve should be completely open at » 25 in. of Hg.
- Experience has shown that the vacuum in the trapped
volume of the closed L.E. ball valve will degrade
during the period the valve is closed. When the
tube/beamline vacuum is at 100 millitorr open the
ball valve and allow the gas load to be pumped by
the Sputter Source diffusion pump.
- Switch the gas security ball valves at the vault
control panel to the protected position with the
key switch. Put the key back in the red box under
the console in the Control Room.
- After the tube vacuum has dropped to 50 millitorr
close the 1 1/4" manifold ball valve and open the
both cryopump gate valves. Remove the pumping
station and return it to where it was found.
- Turn on the Low Energy and High Energy Penning
gauge controllers.
- Turn the L.E. and Cup 1 controllers back on and
reconnect the 300 V dc suppression battery coax
cable to the L.E. cup.
- Open the HE fast valve and close the hand valve
before the 90° magnet.
- Place the SNICS source exit, baffle and backing
valves back in the protected mode and close the
exit valve.
TUBE VOLUME DATA
L.E. valve and H.E. Fast Valve no. 1 closed along with
the associate beamline cryopump valves.
Volume for Pressure Rise Test:
Accel.Tubes: |
6" inside dia., 50' long |
| (p32) x (50 x 12) = |
| 28.26 x 600= | 16980 cubic inches |
L.E. Ext.: |
8" dia. and 39" long |
| 50.27 x 39 = | 1960 cubic inches |
4" dia. and 62" long |
| 12.57 x 62 = | 780 cubic inches |
H.E. Ext.: |
2" dia. and 39" long |
| 6.28 x 39 = | 240 cubic inches |
| 6" dia. and 32" long |
| 28.27 x 32 = | 900 cubic inches |
--------- |
TOTAL: | | 20.86×103 cubic inches
|
Pressure Rise Data From '92:
Pressure Rise = 2 ×10-4 = 0.2 microns, Time = 52 mins. = 3120 secs.
Conversion Factors:
1 cubic inch = 16.39 cc.
Volume = 339.93 x 103 » 340 Litres
Leak Rate = Volume×DPressure/Dt » 0.02lms
28 Tandem Pressure Vessel Sulfur Hex Alarm Circuit Description
The alarm has been set to trip at 75 PSIG and is intended to safeguard
the gas inventory while in the Tandem. Should a substantial (not just
cold gas) change in the pressure be noted or if the panel alarm begins
to annunciate immediately call a member of the staff. Not only is the
SF6 inventory expensive ($70,000) but also is very heavy and
will displace air which could possibly lead to asphyxiation. Do not linger
in enclosed areas common to the gas leak. Sulfur Hexaflouride, SF6,
is, however, nontoxic.
The alarm can be muted at the front panel, but the visual LED will continue
to flash as long as the pressure is below the set point value. For extended
tank openings the power switch can be turned off.
The pressure and temperature transducers are mounted to the flange on
the southern most top tank port. The circuit box adjacent to the flange
should be turned on and plugged into a source of 110Vac. The transducers
output is directed to the Control Room panel for display. Pressures below
atmospheric are indicated by a negative sign with -14.8 psi being the lower
limit of the transducers operating range.
The tank pressure is also indicated by two Bourdon tube, mechanical
pressure gauges and a Varian 501 Thermocouple gauge located at the H.E.,
West side of the pressure vessel. These gauges are independent of the
alarm circuit. The error between the pressure indications in the Control
Room with some of the others can be as high as 11%.
To reset the trip point to some other value, follow this procedure:
- At the back of the Pressure Vessel panel is a
circuit board with a toggle switch position labeled
calset, move the switch to that position. While
observing the front panel pressure indication,
adjust the cal potentiometer until the desired
pressure at which to trip is displayed.
- Also on the circuit board is a potentiometer
labeled trip, adjust this potentiometer until alarm
sounds and the front panel LED is flashing.
- Place the toggle switch in ``1." back to the normal
position. The panel pressure display should again
indicate the current tank pressure.
29 Voltage Conditioning the Tandem
After the machine has been opened for an extended period it is often
noted that the machine will not return to the previously reached voltages
and run stability. Letting up the accelerator tubes to atmospheric pressure
for installation of new equipment, replacement of the stripper foil supply
or other work also contributes to the degradation of the voltage holding
capability of the machine. Preferably, the required terminal voltage for
the experiment subsequent to a tank opening will be somewhat less than
those reached previous to the opening. Regardless of the voltage requested,
it should be assumed that some conditioning will take place and some care
should be taken when first bringing up the terminal voltage. Also, the
conditioning should be carried out until a voltage of at least 250KV over
the experimenter's requested voltage is attained. As the machine conditions,
the required charging current to attain a specific voltage will typically
decrease as corona sites on the column and other high voltage surfaces
begin to dissipate allowing more current to flow through the resistance
grading.
The machine should be set up to condition by first withdrawing the corona
probe to the tank wall. The H.E. faraday cup should be inserted and the
beam current integrator set to measure picoamperes of cup current. The
integrator upper limit alarm should be adjusted to mid
scale so that meter excursions will sound the alarm. The Capacitive Pick
Off (CPO) trace should be displayed on an oscilloscope as well as recorded
by the chart recorder. Since the machine is being conditioned the Terminal
Potential Stabilizer (TPS) feedback is not necessary when charging the
terminal so the Control and CPO Gains should be kept at zero. The TPS is,
however, used for monitoring the Terminal Voltage and the chain charging
trip feature it allows should be employed. By zeroing out the GVM error
with the Terminal Reference Potentiometer, the increase in terminal potential
for a fixed upcharge setting can be displayed as the ``error" grows, but
keep in mind the under/over protection circuit set point may be reached.
Evidence of conditioning below 6MV is not common and voltage stability
problems at this potential (sparking) are indicative of greater problems
and a tank opening may be necessary. In general, any voltage instabilities
associated with the terminal can be considered signs of conditioning; whether
or not the voltage stability improves or persist, short of a mechanical/electrical
failure, determines the length of the conditioning period and its success.
At higher voltages the instabilities associated with conditioning become
more evident. Since the capacitive energy residing in the charged terminal
and column is strongly dependent on the voltage (CV2/2), more caution
should be used when conditioning at higher voltages as the discharges become
more destructive. When heavy conditioning begins to occur, maintain the
current voltage until the conditioning events begin to subside. Voltage
increases in steps of 200KV is suggested. If concern that damage is being
done to the accelerator while attempting to condition (excessive sparking
for example), please err on the side of caution and consult the staff.
Indications of Conditioning:
- Voltage instabilities indicated by the CPO either at the oscilloscope
or the chart recorder.
- Current indications by the beam current integrator.
- Fluctuations of the terminal voltage indication by the TPS that are
fast and greater than 20KV.
- Sparking of the machine, may or may not be audible, but will usually
trip the under/over protection circuit. There are in general three types
of sparks. Tank and Column sparks both occur in the SF6 gas.
The first is a discharge between the column and the tank wall and the other
is along the column structure. Tube sparks occur within the evacuated
space of the accelerator tubes and across tube electrode/insulators gaps.
- Vacuum fluctuations at either the H.E. or L.E. end of the machine as
indicated by the control room penning gauge meters.
- Radiation emissions from the machine as indicated by the control room
gamma/x-ray meter. Should these be in short bursts separated by even longer
intervals and appear to be subsiding, then maintaining that voltage and
waiting for improved stability is the suggested course of action. However,
should the radiation persist at levels greater than 10 mREM and be
steady, the machine should be turned off and the staff notified.
30 Worthington Compressor
The Worthington compressor was installed in the early '70s. It is a
two stage oiless compressor with teflon piston rings and metallic reed
valve assemblies. In 1995 the Dresser Rand was the current spare parts
supplier (tel.1-800-634-5565). The compressor model no. is 12 1/2 X 5
X 13 HB B-2 and the serial no. is L89186. The compressor is driven by
a 125 HP 3-phase motor coupled by belt and pulley. The internal connecting
rod and crank do require lubrication and the recommended
lubricant is ISO-VG-150; AGMA Grade 4.
The compressor is cooled with well water which is circulated through
the water jacket surrounding the compressor cylinders and the heat exchanger.
If the well water supply should fail the supply automatically changes over
to the city water supply. The discharge from the compressor is sent to
the dump well unless a valve change is made to route the water to the storm
drain. The two labeled valves in the Gas Handling Room near the compressor
need to be changed to allow the rerouting. After conditions return to
normal and the well supply becomes available again, changes should be made
to reroute the well water from dumping down the storm drain;
the aforementioned valves will need to be put back in the original
state. The switch from city water to well water supply is again automatic.
31 EMERGENCY VALVE CLOSURES
If during a gas transfer the compressor should stop, a seal fail or
some type of major leak of SF6 start, it is important to safeguard
the gas inventory. Also, at any time should a SF6 loss due
to a failure on the Tandem pressure vessel or the storage tank and any
of the directly attached valves occur a transfer of the SF6 inventory is
suggested immediately. This, however, should not take precedent over safety
as large quantities of SF6 can displace life sustaining air.
Depending on where one is in the gas transfer the compressor may or may
not be running; the response depends on whether the compressor is running.
Below are the responses to three sets of circumstances that may confront
the operator; some valves may or may not already be closed. The valves
affected in the Gas Handling Rm. are shaded red in the preceding room layout.
After the crisis has passed and the transfer piping schematic is consulted
a more sensible arrangement of valves may be preferred.
- COMPRESSOR IS OFF (EQUALIZING GAS) AND A LARGE LEAK IS DETECTED.
Valve (close in order) | Location |
LE Tank Valve | Tandem Vault |
HE Tank Valve | Tandem Vault |
Valve 45 | Outside atop the bottom white |
| storage tank |
- COMPRESSOR HAS FAILED DURING THE GAS TRANSFER AND IS OFF
THERE IS NO LEAK DETECTED
Valve (close in order) | Location |
Valves 5&6 | Gas handling room, orange piping on |
| the W. floor between the |
| back pressure regulator and compressor |
Valve 20 | Gas handling room, yellow |
| piping exiting the surge tank |
Valve 2 | Gas handling room, orange
piping on |
| the W. floor between the back pressure |
| regulator and surge tank |
LE Tank Valve | Tandem Vault, S. end |
Pump pit pneumatic valve | Tandem Vault pump pit |
HE Tank Valve | Tandem Vault, N. end |
Valve 40 | Gas Handling Rm., S. wall |
Valve 41 | Gas Handling Rm., S. wall |
- COMPRESSOR IS ON AND A LARGE LEAK IS DETECTED
Valve(close in order) | Location |
Valves 5&6 | Orange piping on the W. floor |
| between the back pressure |
| regulator and compressor |
Valve 20 | Gas handling room, yellow |
| piping exiting the surge tank |
Turn the compressor off at the control panel |
Valve 2 | Gas handling room, orange piping on the |
| W. floor between the back pressure |
| regulator and surge tank |
LE Tank Valve | Tandem Vault, S. end |
Pump pit pneumatic valve | Tandem Vault pump pit |
HE Tank Valve | Tandem Vault, N. end |
Valve 45 | Outside atop the bottom white |
| storage tank. |
32 Equalizing the SF6 gas to the outside Storage Vessel
Time: » 25 minutes. Change in Pressure: » 80
to » 50 lbs/in2.
Ensure these valves are closed before beginning
the gas transfer. Refer to the locator map for their approximate location:
38, 39, 43, 47, 35, 36, 4, 6, 13, 46, 40
- In the Control Room, turn off the power to the
Terminal Potential Stabilizer panel and withdraw the
Corona Probe.
- In the Tandem Vault, open the H.E. Tandem gas valve at
the bottom of the North end of the tank. Ensure the
tank lights are turned off.
- Open the L.E. Tandem gas ball valve at the bottom of
the tank South end.
- Open valve 41, located at the S. wall of the gas
handling room, to allow the gas to equalize into the
Storage Vessel.
- Open valve 29 to collect the gas left in the piping
from last gas transfer. The valve will probably be
open already. If gas is not heard flowing it may be
that valve 3, on the East side of the Tandem is
closed, open it.
- In the Control Room, remove the control power key and
place it on top of the electronic rack.
- Switch the Gas Pressure Alarm panel to the mute mode.
- When gas is no longer heard flowing through the
piping, go to the next step.
33 Compressing the SF6 to the Storage Vessel
Time: » 90 minutes. Change in Pressure: » 50 lbs/in2 to » 23" Hg.
- Close the two brass Hygrometer shutoff valves. One is
behind the green panel at the H.E. beamline support
and the other is on the H.E. Tandem end plate.
- Close valve 41, S. wall of Gas Handling Room, to route
the gas from the Tandem through the compressor to the
Storage Vessel.
- Open valve 40 to allow the gas from the compressor to
fill the Storage Vessel.
- Turn on the compressor breaker switch at S.E. wall in
the Gas Handling Room and ensure cooling water flows
through the compressor at the flow gauges located at
the N. end of the compressor.
- Quickly open valve 2, orange piping on the floor by
the back pressure regulator,as soon as the compressor is
started. Press the start button on the breaker
panel; the compressor will make quite a bit of noise
when just starting. The compressor will not start with
a positive input pressure. The input pressure to the
compressor is indicated by the pressure gauge at the
No.2 five micron filter, painted orange and West of
the yellow surge tank.
- Open valve 4 and then 5 slowly, the back pressure
regulator should ensure the input pressure to the
compressor does not go positive. Should a failure
occur and the input pressure become positive the
compressor will shut down.
- SF6 is fed back into a shaft isolation chamber to
prevent air creeping along the shaft into the gas
inventory. A pressure gauge located on the
compressor, West of the No.2 filter, should indicate a
slightly positive pressure ( < 3 lbs/in2. Ensure this
is the case.
- After » 30 minutes the back pressure regulator can be
bypassed to increase the compressor throughput. Don't
allow the input to the compressor at the 5 micron
filter to rise above 8" Hg or the heat exchanger
between the two pumping stages to go over 45 lbs/in2
(top gauge on compressor). The bypass is allowed by
slightly opening valve 6 in steps to maintain the 8" Hg
input pressure; eventually the valve will be
completely opened.
- Run the compressor until the Tandem's pressure gauge
at the H.E. end registers 23" Hg (approximately -10.8
psig on the Control Room SF6 parameter panel
display). The ball valve to the right of the gauge
may need to be opened. Proceed to the next section.
34 Vacuum Pump boosting for the Compressor
- At the H.E. end of the Tandem, connect the Varian 501
gauge controller to the thermocouple. Next to the
controller, reset the Rootes Blower run time meter to
zero.
- Close the H.E. Tandem gas valve.
- In the Gas Handling Room, close valves 4, 5 and 6.
- Open valve 20 slightly and ensure the surge tank
pressure begins to drop. The input to the compressor
must remain less than atmospheric or the compressor
will shut down.
- The procedure for starting the vacuum pumps follows;
they are located below the Tandem in the pit.
- Ensure valve X2, a 1/2" ball valve
between the Rootes blower and the Kinney, is
closed.
- Open valve X1, located on the pit wall in the
Southwest corner, to vent the stagnant air left
in the piping and Rootes Blower.
- Start the mechanical pump by depressing the push
button located on the panel to the left of the
pumps. Hold the button down for at least 3
seconds to ensure the cooling water flow switch
latches the pump run contacter. Allow the
mechanical pump to run for 30 seconds then
continue to the next step.
- There are two switches associated with the
Rootes Blower. The upper most switch of the
two is a wall type light switch that allows
power to the second switch that is a three
position switch. The wall light switch must be
flipped up to enable the Rootes to come on.
Slide the three position switch to the bottom
position, manual mode; the Rootes will come on.
Allow it to run for 30 seconds and then slide
the three position switch to the top, SF6
automatic mode. The Rootes will come on when
the Varian 501 controller set point one is
reached.
- Wait for the blower shaft to slow and then close
valve X1.
- Open V10 which directs the discharge of the
vacuum pumps to the compressor input.
- Open the Tandem's pneumatic valve by turning the key
at the control panel and flipping the switch located
near the valve on the flexible wire conduit.
- In the Gas Handling Room, open valve 20 the rest of
the way, yet maintain a pressure below 8" Hg at the
5 micron filter.
- When the Tandem pressure reaches 4.6 torr, the set
point, the thermocouple controller will automatically
activate the Rootes blower. If the Tandem pressure is
too high the Rootes will trip its circuit breaker and
must be reset behind the control panel.
- At » 200 microns begin the shutoff procedure. The
Control Room SF6 parameter panel display range of
sensitivity will end at approximately -14.2 psig.
35 Shutoff Procedure
- Close the Tandem pneumatic valve in the vault pit. Use
both the toggle switch and the key.
- Turn off the Rootes Blower wall light switch and slide
the 3-position switch to the manual mode, the bottom
position. Allow the blower to slow.
- Close V10 which isolates the input to the compressor.
- Open the l/2" yellow ball valve labeled X2 between the
Rootes blower and the Kinney pump.
- Turn off the mechanical pump by depressing the stop
button.
- Close valve X2 when air no longer flows.
- In the Gas Handling Room, close V20 yellow piping.
- Quickly close V2 orange piping,
after the compressor is turned off by depressing the push button.
Turn the breaker to off after the valve is closed.
- Close V40, S. wall in the Gas Handling Room.
- Disconnect the thermocouple controller from the gauge
head at H.E. end of the Tandem.
36 Venting the Tandem to Air
Time: » 30 minutes. Change in Pressure: » 150 millitorr to 1 atmosphere.
- Turn the Tandem ports to the open position. The
vacuum will keep the ports sealed shut.
- Partially open valve 43, red piping in gas handling
room. As the flow is heard slowing, open valve 43
more. Continue until completely open.
- After the ports are open close valve 43.
- Place the fan in the Tandem L.E. port and turn on so
that air is pulled out through the L.E. port.
- Turn on tank lights. The Tandem is ready for floor
boards and/or working inside.
37 Removing Air from the Tandem
Time: » 14 hours (overnight). Change in Pressure: 1 atmosphere
to » 25 millitorr.
- Remove all items brought into the Tandem, wipe the
terminal off with alcohol and paper towels, remove the
floor boards and sweep the bottom of the tank clean.
Ensure no debris is left on the Tandem pneumatic valve
flapper surface inside the tank; use the ShopVac
vacuum cleaner. Turn the Tandem tank lights off.
- Shut the Tandem port doors and turn them partially
closed. It will be difficult to completely close them
until a vacuum is established. Make an attempt to
close them at 14" Hg; typically, the lower the vacuum
reached the easier it is to turn close the port doors.
- Ensure that valves 2 and 43 in the Gas Handling Room
and 10 and 11 in the Tandem pump pit are closed.
- Ensure that valve X2, a 1/2" ball valve between the
Rootes blower and the Kinney pump, is closed.
- Open valve X1 to allow pumped air to exit the
building.
- Start the mechanical pump by depressing the push
button located on the panel to the left of the pumps.
Hold the button down for at least 3 seconds to ensure
the cooling water flow switch latches the pump run
contacter.
- There are two switches associated with the Rootes
Blower. The upper most switch of the two is a wall
type light switch that allows power to the second
switch that is a three position switch. The wall
light switch must be flipped up to enable the Rootes
to come on. Slide the three position switch to the
middle position, air automatic mode. The Rootes will
come on when the Varian 501 controller set point two
is reached.
- Open the Tandem pneumatic valve by turning the key
at the control panel and flipping the switch located
near the valve on the flexible wire conduit.
- Connect the Thermocouple controller to the gauge head
at the H.E. end of the Tandem.
- Allow the Tandem to be pumped on over night to remove
absorbed gases and water vapor.
- In the morning the Tandem vacuum should be at » 25
millitorr. Close the pneumatic valve with the key and
toggle switch. Turn off the Rootes Blower wall light
switch and return the three position switch to the
manual mode, slide to the bottom position. Allow the
blower to slow.
- Close X1 which allows the pumps to exhaust outside the
building.
- Open the l/2" yellow ball valve labeled X2 between the
Rootes blower and the Kinney pump.
- Turn off the mechanical pump by depressing the stop
button.
- Close valve X2 when air no longer flows.
- Check and top off if necessary the Rootes blower and
Kinney pump oil.
38 Equalizing SF6 into the Tandem
Time: » 60 min. Change in Pressure: » 25 millitorr
to » 50 lbs/in2.
- Close the ball valve before the +30 psi -30" Hg gauge
at the H.E. end of the Tandem.
- Disconnect the Thermocouple controller lead from the
gauge head.
- Ensure valve 41, in the Gas Handling Room behind the
yellow paint cabinet, is closed.
- Open valve 39, red piping to the left of the grey
drier/desiccant tanks.
- Open valve 40 (next to 41) partially, especially on
cold mornings to prevent thermal shock to the
accelerator column. As the flow rate is heard
slowing, rotate the ball valve open more.
39 Compressing SF6 into the Tandem
» 4 hours » 50 to » 90 lbs/in2
- Close valve 40, S. wall of Gas Handling Room.
- Open valve 41 to route the gas from the Storage Vessel
though the compressor to the Tandem.
- Turn on the compressor breaker switch at S.E. wall in
the Gas Handling Room and ensure cooling water flows
through the compressor at the flow gauges located at
the N. end of the compressor.
- Quickly open valve 2, orange piping on the floor by
the back pressure regulator, as soon as the compressor
is started. Press the start button on the breaker
panel; the compressor will make quite a bit of noise
when first starting. The compressor will not start
with a positive input pressure. The input pressure to
the compressor is indicated by the pressure gauge at
the No.2 five micron filter, painted orange and West
of the yellow surge tank.
- Open valve 4 and then 5 slowly to ensure the input
pressure to the compressor does not go positive; this
will result in the shut down of the compressor.
- SF6 is fed back into a shaft isolation chamber to
prevent air creeping along the shaft into the gas
inventory. A pressure gauge located on the
compressor, West of the No.2 filter, should indicate a
slightly positive pressure ( < 3 lbs/in2. Ensure this
is the case.
- After » 30 minutes the back pressure regulator can be
bypassed to increase the compressors throughput
capacity. Do not allow the input to the compressor at
the 5 micron filter to rise above 8" Hg or the heat
exchanger between the two pumping stages to go over 45
lbs/in2 (top gauge on compressor). The bypass is
allowed by slightly opening valve 6 in steps to
maintain the 8" Hg input pressure; eventually the
valve will be completely opened.
- Run the compressor until the input pressure at the 5
micron filter registers » 27" Hg
- Close valve 41.
- Close valves 4, 5 and 6.
- Stop the compressor and quickly close valve 2. Ensure
the breaker is turned off after the valve is closed.
- Close valve 39.
- Close the L.E. Tandem gas valve.
- Open the two brass Hygrometer shutoff valves. One is
attached to the back of the green panel at the
beamline support and the other to the H.E. Tandem end
plate.
- Turn the Gas Pressure Alarm panel back to ``aural" in
the Control Room.
The gas transfer is complete.
40 Adding SF6 to the Inventory from Cylinders
SF6 is usually delivered in cylinders that come in two sizes:
A and B. The cylinders are filled with liquid and their pressure will
be the SF6 vapor pressure for the cylinder temperature. Due
to the latent heat of vaporization, it will be necessary to add heat to
the cylinder as the liquid changes to the gaseous phase and fills the Tandem.
A typical pressure encountered would be » 270 lbs/in2.
At this vapor pressure the majority of the cylinder contents can be added
directly to the tandem. When all the liquid has evaporated and the cylinder
pressure matches the Tandem's additional effort is necessary to empty the
remaining cylinder contents. The last bit of gas can be sent to storage
for recovery at the next gas transfer or the SF6 compressor
can be used to add directly to the Tandem inventory.
40.1 Adding SF6 directly to the Tandem From Cylinders
- Remove the cylinder caps and the plastic thread
protector that often accompanies the valve. Attach
the SF6 cylinders to the flexible lines at the fill
manifold in the Gas Handling Room; the cylinder
threads are left handed. Attach the cylinder heaters
to the bottom of the cylinders. If plastic mesh
surrounds the bottle, roll it back on itself to ensure
it does not melt.
- Open the cylinder and fill line valves. Open the
valve isolating the pressure gauge at the end of the
fill manifold.
- Close valve 45 located outside on top of the storage
tank. Inside the Gas Handling Room ensure they're
closed or close valves 13, 2, 43, 47, 4 and 6. In the
Tandem Vault ensure valve 3, on the East side of the
Tandem, is closed.
- In the Tandem Vault open the L.E. valve. In the gas
handling room open valves 41, 40, 39, 29 and 46. The
cylinders should now be emptying and will begin
cooling down.
- Turn on the heaters at the breaker panel around the
corner from the fill station and leave them on until
the cylinders either feel warm approximately 12" up
from the heaters or SF6 no longer flows from the
cylinders.
- When the cylinders' pressure has equalized with the
tandem pressure, close valve 40. Continue to the next
step to remove the remaining SF6.
40.2 Removing the SF6 remaining in the cylinders at
Tandem pressure
These two procedures assume the valves are still in the state they were
left in when adding the cylinder SF6 to the Tandem. Part A
describes the procedure for transferring the residual cylinder gas
with the compressor to the Tandem. Part B describes the procedure for
transferring the residual cylinder gas to storage for addition to the
gas inventory at the next gas transfer.
Part A, to the Tandem:
- Turn on the compressor breaker switch at S.E. wall in
the Gas Handling Room and ensure cooling water flows
through the compressor at the flow gauges located at
the N. end of the compressor.
- Quickly open valve 2, orange piping on the floor by
the back pressure regulator, as soon as the compressor
is started. Press the start button on the breaker
panel; the compressor will make quite a bit of noise
when just starting. The compressor will not start
with a positive input pressure. The input pressure to
the compressor is indicated by the pressure gauge at
the no.2 five micron filter, painted orange and West
of the yellow surge tank.
- Open valves 4 and 5 while keeping the heat exchanger
below 50 lb/in2. Valve 6, the regulator bypass, can
be utilized yet keep the input to the compressor below
atmospheric.
- Pump on the cylinders until the compressor is at 28"
Hg. Often there is a check valve installed on the
cylinders that prevent a vacuum being drawn which may
cause contamination of the cylinder, close valve 46 to
check the cylinder pressure. Ensure the cylinders are
left with little pressure by cycling valve 46 until
satisfied.
- Quickly close valve 2 orange piping, after the
compressor is turned off by depressing the push
button. Turn the breaker to off after the valve is
closed.
- In the Tandem Vault close the L.E. valve and open
valve 3. In the Gas Handling Room close valves 4,5,
6, 41, 39, 46, fill line valves, cylinder valves and
gauge valve.
- Open valve 45 on top of the outside storage tank.
- Return the empty cylinders to outside storage for
return. Use the chains provided on the West side of
the Gas Handling Room loading dock to secure the
cylinders.
Part B, To storage:
- In the Tandem Vault close the L.E. valve. In the gas
handling room close valves 41 and 39.
- Open valve 45 on top of the storage tank outside.
- Back in the Gas Handling Room, open valve 41 to allow
the SF6 to flow to the storage tank. Often there is a
check valve installed on the cylinders that prevents a
vacuum being drawn which may cause contamination of
the cylinder, close valve 46 to check the cylinder
pressure. Ensure the cylinders are left with little
pressure by cycling valve 46 until satisfied with the
cylinder residual.
- After the cylinders are emptied close the individual
cylinder and manifold valves. Close valve 41.
- In the Tandem Vault open valve 3.
- Return the empty cylinders to outside storage for
return. Use the chains provided on the West side of
the Gas Handling Room loading dock to secure the
cylinders. A call to the supplier of the SF6 will
hasten the cylinder collection.
41 SF6 Gas Drying
The three major components of the gas drying system are the blower,
desiccant tanks and hygrometer. SF6 from the accelerator is
removed at the L.E. valve passed through the dryer circuit and then returned
through the H.E. valve via the blower. The desiccant beds will remove
water from the gas as it is continuously cycled until a sufficiently low
dew point or water vapor content is reached, » 10 ppm. The desiccant
in the tanks does, however, adsorb a finite amount of water and will require
reactivating when it has become saturated. The desiccant is reactivated
by passing hot air through the tank evaporating the water that was removed
from the SF6.
Reactivating the Gas Dryer
- Ensure valves 35, 37 and 47 are closed.
- Inspect the pressure gauges atop the silver/grey
desiccant tanks. If they are pressurized slowly
open valve X-3 to release the pressure.
- After the tank pressure is released, open valve X-4
and turn on the power at the red electronics box to
the north of the desiccant tanks. A blower should
come on along with the heater elements; the red
light atop the electronics box should be
illuminated.
- Allow the reactivation cycle to continue; it will
automatically shut off when the desiccant tank
temperature reaches the thermostat set point, » 3
hours.
- Close the two valves X -3 and -4, and turn off the
switch at the electronics box. Allow the desiccant
tanks to cool to room temperature before attempting
to dry the SF6.
Recirculating the Gas
This procedure assumes the Tandem has been secured in the normal fashion
after being gassed-up and the dryer has been reactivated.
- Ensure valves 35 (blue piping Gas Handling Room),
29 (red piping Gas Handling Room), 3 (orange piping
E. side of Tandem), X-3 and X-4 (gray piping gas
handling room) are CLOSED.
- Open valves 36, 37, 47 (blue piping gas handling
room), the L.E. Tandem valve and H.E. Tandem valve.
- The power switch for the blower used to recirculate
the SF6 through the desiccant tanks is located at
the fuse box to the left of the entrance to the
Tandem Vault L.E. end labeled Recirculator. Three
push buttons are located at the bottom of box,
also, a grey extension cord should be hanging from
the bottom, plug the cord into one of the outlets
immediately to the right. Depress the start button
to turn on the blower in the blue tank in the N.E.
corner of the Gas Handling Room.
- Allow the gas to recirculate through the dryer
circuit until the hygrometer indicates a dew point
or water vapor concentration that is acceptable
(below -50°f)
- Turn off the blower and close valves 36, 37, 47,
the L.E. Tandem valve and H.E. Tandem valve.
- Ensure that valves 3 and 29 are left open.
42 SF6 Leak Checking Gun
When ever a SF6 leak is suspected, or when making routine
checks after gas transfers the SF6 leak detector or leak checking
gun can be used to localize small, inaudible leaks as small as
0.2 cc/sec. Normally the gun is kept in the gray Tandem Cabinet in the NW corner of
the control room. Detailed instructions concerning the gun are included
in the black carrying case. A general description for setting the detector
up follow and are included in the carrying case.
- Ensure there is at least 150 lbs. of argon pressure
in the cylinder. Open the cylinder valve to check
this.
- On the gun, turn the selector switch to the check
volts position and squeeze the guns trigger; the
meter should indicate between 60-80 divisions
unless the batteries need replacing.
- The Detector will require a purge period of five
minutes or so. Press the check detector button
while simultaneously squeezing the trigger; the
meter should indicate 0 before the purge and 40 or
more divisions afterwards. It does not some
maintenance of the gun is in order.
- Turn the selector switch to the appropriate
sensitivity and adjust the zero. Normally I adjust
it to zero while at the highest sensitivity in the
Control Room. The zero setting will be altered
some as the detector cell cleans up.
- Check the pressure vessel for leaks by bringing the
gun barrel or tip into close proximity to areas
suspected of leaking SF6.
- Ensure the cylinder is turned off before putting
the leak checking gun in the carrying case an back
into the gray cabinet.
File translated from
TEX
by
TTH,
version 2.92.
On 31 Jul 2001, 16:07.